Eaton PT 10 Instruction Manual page 39

Power trip (pt) units
Hide thumbs Also See for PT 10:
Table of Contents

Advertisement

Table A5. Setpoints Group 5: Protection Group.
Mask
Register
Bit Field
Field
403000
15-0
0xFFFF
403001
15-0
0xFFFF
403002
2-0
0x000F
403003
11-0
0x0FFF
403004
11-0
0x0FFF
403005
2-0
0x000F
403006
11-0
0x0FFF
403007
11-0
0x0FFF
403008
2-0
0x000F
403009
7-0
0x00FF
403010
11-0
0x0FFF
403011
2-0
0x000F
403012
7-0
0x00FF
403013
11-0
0x0FFF
403014
2-0
0x000F
403015
15-0
0xFFFF
403016
11-0
0x0FFF
403017
0
0x0000
403018
0
0x0000
403019
2-0
0x000F
403020
11-0
0x0FFF
403021
2-0
0x000F
403022
11-0
0x0FFF
Setpoint Name
Password
Group 5 = Protection
Over-Voltage Protection Setting
Over-Voltage Protection Threshold
Setting
Over-Voltage Protection Time Setting
Under-Voltage Protection Setting
Under-Voltage Protection Threshold
Setting
Under-Voltage Protection Time
Setting
Voltage Unbalance Protection Setting R/W
Voltage Unbalance Protection
Threshold Setting
Voltage Unbalance Protection Time
Setting
Current Unbalance Protection Setting R/W
Current Unbalance Protection
Threshold Setting
Current Unbalance Protection Time
Setting
Reverse Power Protection Setting
Reverse Power Protection Threshold
Setting
Reverse Power Protection Time
Setting
Invalid
Invalid
Phase Loss Protection Setting
Phase Loss Protection Time Setting
Over-Frequency Protection Setting
Over-Frequency Protection Threshold
Setting
Appendix A - Modbus Communication Port Setting
R/W
Format
W
R/W
R/W
Encoded
R/W
Unsigned
R/W
Unsigned
R/W
Encoded
R/W
Unsigned
R/W
Unsigned
Encoded
R/W
Unsigned
R/W
Unsigned
Encoded
R/W
Unsigned
R/W
Unsigned
R/W
Encoded
R/W
Unsigned
R/W
Unsigned
R
R
R/W
Encoded
R/W
Unsigned
R/W
Encoded
R/W
Unsigned
PT UNIT USER MANUAL APRIL 2023 www.eaton.com.cn
Value Definition
Factory default = 0000
0x05FF
0 Trip
1 Alarm
2 OFF
180~720, step is 1 (Unit: V)
1~300, step is 1 (Unit: seconds)
0 Trip
1 Alarm
2 OFF
60~670, step is 1 (Unit: V)
1~300, step is 1 (Unit: Seconds)
0 Trip
1 Alarm
2 OFF
5~25, step is 1 (Unit: %)
1~300, step is 1 (Unit: Seconds)
0 Trip
1 Alarm
2 OFF
5~25, step is 1 (Unit: %)
1~300, step is 1 (Unit: Seconds)
0 Trip
1 Alarm
2 OFF
1~65500, step is 1 (Unit: kW)
1~300, step is 1 (Unit: Seconds)
0 Trip
1 Alarm
2 OFF
1~240, step is 1 (Unit: Seconds)
0 Trip
1 Alarm
2 OFF
40~70, step is 1 (Unit: Hz)
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pt 20Pt 25