Eaton PT 10 Instruction Manual page 40

Power trip (pt) units
Hide thumbs Also See for PT 10:
Table of Contents

Advertisement

Appendix A - Modbus Communication Port Setting
Table A5. Setpoints Group 5: Protection Group. (continued)
Mask
Register
Bit Field
Field
403023
11-0
0x0FFF
403024
2-0
0x000F
403025
11-0
0x0FFF
403026
11-0
0x0FFF
403027
2-0
0x000F
403028
2-0
0x000F
403029
2-0
0x000F
403030
11-0
0x0FFF
403031
11-0
0x0FFF
403032
11-0
0x0FFF
403033
15-0
0xFFFF
403034
2-0
0x000F
403035
15-0
0xFFFF
403036
15-0
0xFFFF
36
PT UNIT USER MANUAL APRIL 2023 www.eaton.com.cn
Setpoint Name
Over-Frequency Protection Time
Setting
Under-Frequency Protection Setting
Under-Frequency Protection
Threshold Setting
Under-Frequency Protection Time
Setting
Phase Sequence Protection Setting
Phase Sequence Protection Phase
Sequence Setting
Current Demand Protection Setting
Current Demand Protection
Threshold Setting Phase A
Current Demand Protection
Threshold Setting Phase B
Current Demand Protection
Threshold Setting Phase C
Current Demand Protection Time
Setting
Power Demand Protection Setting
Power Demand Protection Threshold
Setting
Power Demand Protection Time
Setting
R/W
Format
R/W
Unsigned
R/W
Encoded
R/W
Unsigned
R/W
Unsigned
R/W
Encoded
R/W
Encoded
R/W
Encoded
R/W
Unsigned
R/W
Unsigned
R/W
Unsigned
R/W
Unsigned
R/W
Encoded
R/W
Unsigned
R/W
Unsigned
Value Definition
2~50, step is 1 (indicating 0.2~5 Seconds)
0 Trip
1 Alarm
2 OFF
40~70, step is 1 (Unit: Hz)
2~50, step is 1 (indicating 0.2~5 Seconds)
0 Trip
1 Alarm
2 OFF
0 A-B-C, positive sequence
1 A-C-B, negative sequence
0 Trip
1 Alarm
2 OFF
20~100, step is 1 (indicating 0.2I
~1.00I
n
20~100, step is 1 (indicating 0.2I
~1.00I
n
20~100, step is 1 (indicating 0.2I
~1.00I
n
15~1500, step is 1 (indicating 15~1500 seconds)
0 Trip
1 Alarm
2 OFF
1~65550, step is 1 (indicating 1~65550kW)
15~1500, step is 1 (indicating 15~1500 seconds)
)
n
)
n
)
n