Commissioning/Operation; Io-Link Version; Programming - Barksdale BDS3000 Operating Instructions Manual

Dual differential pressure switch

Advertisement

Electrical connection is to be carried out dependent on the type of switch (see name label) according
to the chart below. Improper connections may cause malfunctions or incorrect switch outputs and
damage to the unit.
Electrical connection
Plug M 12x1
Model with 2 switch
4/5/-pin
point
Signal output code 1, 7
+Ub
1
2
SP2
3
OV
4
SP1 / IO link'
-
5
*
only code 7 and 8
Plug
6

Commissioning/Operation

The pressure switch may only be commissioned and operated by authorized staff.
CAUTION
Do not put the switch into operation when the switch itself or the connection cable is damaged.
WARNING
Be aware of the fact that in case of operation with higher temperatures the casing surface may
become very hot!
Apply high pressure first, followed by the low reference pressure.
4
Model with 1 switch point
Model with 2 switch point and
and 1 analog output
1 analog output
Signal output code 2, 3
Signal output code 4, 5, 8
+Ub
+Ub
Signal
Signal
0V
0V
SP1
SP1 / IO link'
-
SP2
After having been switched on the switch runs through a self-test. If the software recognizes an
error during the self-test or during operation, this is signaled in the display by "Err" and the
corresponding message, refer to Error list on page 7. The red LEDs S1 and S2 signal the activity
of the two switching points.
Operation is menu-driven via three keys:
CAUTION
Do not use any pointed, hard objects for making entries. The keys may be damaged by pointed,
hard objects.
7

IO-link version

General information
This device features an IO-link communication interface which requires an IO-link capable module
(IO-link master) for operation. The IO-link interface permits direct access to process and diagnostic
data and offers the possibility of parametrising the device during operation. Moreover
communication via a point-to-point connection using a USB adapter cable is possible.
Device-specific information
The IODDs required for the configuration of the IO-link device and detailed information about
process structure, diagnostic information and parameter addresses are available at ->IODD finder
and on https://www.barksdale.de/de/download/iolink/. To find the required information please enter
the order code in the search mask. IO-link devices manufactured before 04-01-2019 do not
support different polarities of the switching outputs.
NOTE: Since process connection, seal and measuring cell have no influence on the IO-link
communication you must replace them by "xx". E.g. BDS375VM0010BP = BDS37xxM0010Bx
TIP: Use the autocomplete function of the IODD finder by entering the article no. character by
character. If your device has been manufactured before 04-01-2019 please take into account that
the proposed device ID begins with 0x070.
8

Programming

Navigation function
Menu descending
Menu ascending
Horizontal movement in menu, select menu item
Parameter change ascending
Parameter change descending
Accept parameter change and return to current menu item
Return to measured value display
,
and
Symbol (keys)
Press
+
simultaneously
5