Mitsubishi Electric PUHZ-ZRP100VKA3 Service Manual page 20

Hide thumbs Also See for PUHZ-ZRP100VKA3:
Table of Contents

Advertisement

Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Indoor unit L-N
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.
*2. Maximum 120 m
*3.The 10 m wire is attached in the remote controller accessory. Maximum 500 m
*4.The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and indoor unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed
flexible cable. (Design 60245 IEC 57)
3. Install an earth line longer than power cables.
8-3. INDOOR – OUTDOOR CONNECTING CABLE
The cable shall not be lighter than design 60245 IEC or 60227 IEC.
Outdoor power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Note: The maximum cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Note: The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
For PUHZ-ZRP200/250YKA2.UK
Cross section of cable
Wire size (mm
Round
Flat
Flat
Round
Note: Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC.
*1 In case that cable with stripe of yellow and green is available.
*2 In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm
*3 In case of regular polarity connection (S1-S2-S3).
*4 In the flat cables are connected as this picture, they can be used up to 30 m.
*5 Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or
materials, etc.
OCH645
*1
*2
*3
*4
*4
*4
*4
Max. 45 m
3 o 1.5 (polar)
1 o Min. 1.5
Number of wires
)
2
2.5
3
2.5
3
1.5
4
2.5
4
ZRP35–140
~/N (single), 50 Hz, 230 V
16 A
3 o Min. 1.5
1 o Min. 1.5
2 o Min. 0.3
2 o 0.3 (Non-polar)
230 V AC
24 V DC
12 V DC
Wire No. o Size (mm²)
Max. 50 m
3 o 2.5 (polar)
1 o Min. 2.5
Wire No. o Size (mm²)
Max. 120 m
2 o Min. 0.3
Polarity
Clockwise : S1-S2-S3
(Pay attention to stripe of yellow and green.)
Not applicable
(since center wire has no cover finish.)
From left to right : S1-Open-S2-S3
Clockwise : S1-S2-S3-Open
(Connect S1 and S3 to the opposite angle.)
S1
S2
S3
2
.
20
Max. 80 m
3 o 2.5 (polar) and S3 separated
1 o Min. 2.5
Not applicable
(3C Flat cable × 2)
L (m)*5
(30)
*1
*4
(18)
*2
(30)
*3