Slip Fitter Models: F1U******S****
Make proper connections inside the junction
base of the slip fitter and tuck any excess
wiring into the junction base. Assure none of
the wiring can be pinched when replacing
cover.
Install the cover and tighten the hardware
using the recommended torque to assure a
proper seal.
Torque: 1 in-lb [1.4 N-m]
Mast Arm Models: F2U******T****
Open the mast arm cover by loosening the
two captive 10-32 screws and pulling the
cover open. Loosen the four ½-13 bolts most
of the way to allow the pole to slide into the
housing.
Slide the fixture onto the pole at desired
incline. The middle "step" represents 0⁰ tilt.
The
other
steps
represent
respectively. Adjust to desired step as
needed. Tighten the four ½-13 bolts evenly
around the pole. Ensure that the clamp plate
remains parallel to the bottom of the mast
arm housing. A two axis bubble level is
included for mounting convenience.
Torque to 29-31 ft-lbs [39.3-42.1 N-m]
4x 1/2 -13 bolts
Feed mains cable through supplied cable
gland and into wire box.
Torque cable gland to 45-55in-lbs[5.2-6.2N-m]
After the fixture has been mounted, snap the
access cover closed and tighten the two 10-
32 captive screws to 30 in-lbs [3.4 N-m]
Note: If the access cover interferes with
mounting the fixture, press on the hinges
towards the top/front of the fixture. The cover
is spring-loaded and will snap out of place. To
reinstall after mounting, align the hinges on
the inclined springs and push towards the
back of the fixture. Cover should snap back
into place.
9100FLM000900 REV E
Page 5 of 10
ProSite Floodlight for UL 1598/1598A
"W" bracket orientation
NOTE: The bracket that is factory installed is
suitable for 2" NPS poles. For 1.25" NPS or 1.5"
NPS poles, the second "W" shaped bracket
found in the box should be used by replacing
the factory-installed bracket. Be sure to reuse
the four ½-13 bolts, flat washers, and lock
washers.
Asymmetric Wide Throw Models:
F2UNJ*********
After installation, remove the 4x rubber optic
protectors and 4x 10-32 screws. These can
then be discarded.
+/-5⁰
tilt
WARNING: The optic features on Asymmetric
Wide Throw models may be very sharp.
Appropriate actions should be taken when
handling the unit in order to prevent injury.
Damage to these sharp optical features will
result in degradation of the light pattern.
Electrical Connections
Bracket Models: F*U******(E/F)****
The terminal block is suitable for multi-
stranded or single core wires. The parameters
can be found in Technical Data.
Push Down Terminal Models: F*U********V**
Push down at the 'cross point', insert wire, and
release.
Conductor Range
0.5-4 mm² [20-12 AWG]
Screw Down Terminal Models: F*U********U**
For input power terminal block, loosen
terminal screw, insert wire, and tighten screw.
Conductor Range
0.5-6 mm² [20-10 AWG]
For dimming & Dali lines, push down at the
'cross point', insert wire, and release.
Conductor Range
0.5-4 mm² [20-12 AWG]
Slip Fitter Models: F1U******S****
All slip fitter models contain lever nut
connectors inside the junction base to make
appropriate connections.
Conductor Range
0.5-4 mm² [20-12 AWG]
Single Phase Connections
The connections are marked on the terminal
block or on a label and are presented in the
table below.
SYMBOL
N
L
N
L
L2
L1
DIM +
DIM -
DALI
0-10 VDC Dimming (If Applicable)
Dimming is controlled by means of a 0-10
VDC signal (to be provided by the installer) to
control the level of dimming. At 10 volts, the
output of the unit is 100%; at 0 volts, the output
will shut off. The DC dimming voltage should
not exceed 15 VDC. Increasing the voltage
from 10 VDC to 15 VDC will not result in
Strip Length
additional light output.
9 mm [0.35 in.]
WARNING: Never connect the dimming wires
to the Hot/Live or Neutral supply wires.
Dialight, 1501 Route 34 South, Farmingdale, NJ, USA 07727
Tel: +1 732 919 3119 Fax: +1 732 751 5778
Strip Length
10 mm [0.39 in.]
Strip Length
9 mm [0.35 in.]
Strip Length
9 mm [0.35 in.]
COLOR
CONNECTION
120-277VAC
GREEN/
EARTH/
YELLOW
GROUND
WHITE
NEUTRAL
BLACK
LIVE
120-250VDC
GREEN/
EARTH/
YELLOW
GROUND
WHITE
-
BLACK
+
347-480VAC
GREEN/
EARTH/
YELLOW
GROUND
RED
LIVE 2
BLACK
LIVE 1
CONTROLS
VIOLET
DIMMING +
GREY
DIMMING -
ORANGE
DALI
OR YELLOW
www.dialight.com