11 MAINTENANCE AND UPKEEP

11.1 Failure information and code

In case the unit runs under abnormal condition, failure protection code will display on both control panel and wired controller,
and the indicator on the wired controller will flash with 1Hz. The display codes are shown in the following table:
Table11-1 SCV-750EB and SCV-900EB and SCV-1400EB and SCV-1800EB
No. Code
75&140 Model Main control Model setting error
1
E0
(Other Model Main control EPROM error)
2
E1 Phase sequence error of main control board check(for 90&180 model)
Communication failure between master and the HMI
3
E2
Communication failure between master and slave
2E2 Communication failure between main board and slave board
4
E3 Total water outlet temperature sensor failure (main unit valid)
5
E4 Unit water outlet temperature sensor failure
1E5 condenser tube temperature sensor T3A failure
6
E5
2E5 condenser tube temperature sensor T3B failure
7
E6 Water tank temperature sensor T5 failure
8
E7 Ambient temperature sensor failure
9
E8 Power supply phase sequence protector output error
10
E9 Water flow detection failure
1Eb-->Taf1 the pipe of the tank antifreeze protection sensor failure
11
Eb
2Eb-->Taf2 cooling evaporator low-temperature
antifreeze protection sensor failure
12
EC Slave unit module reduction
13
Ed system discharge temperature sensor failure
1EE EVI plate heat exchanger refrigerant temperature T6A sensor failure Recovered upon failure recovery
14
EE
2EE EVI plate heat exchanger refrigerant temperature T6B sensor failure Recovered upon failure recovery
15
EF Unit water return temperature sensor failure
16
EP Discharge sensor failure alarm
17
EU Tz sensor failure
P0 System high-pressure protection or discharge
temperature protection
18
P0
1P0 Compressor module 1 high pressure protection
2P0 Compressor module 2 high pressure protection
System low pressure protection(or Severe refrigerant leakage protection
19
P1
only for 75&140 model)
20
P2 Tz total cold outlet temperature too high(for 90&180 model)
21
P3 T4 ambient temperature too high in cooling mode
1P4 System A current protection
22
P4
2P4 System A DC bus current protection
1P5 System B current protection
23
P5
2P5 System B DC bus current protection
24
P6 Inverter module failure
25
P7 High temperature protection of system condenser
26
P9 Water inlet and outlet temperature difference protection
27
PA Abnormal water inlet and outlet temperature difference protection
28
Pb Winter antifreeze protection
29
PC
Cooling evaporator pressure too low
30
PE Cooling evaporator low temperature antifreeze protection
31
PH Heating T4 too high temperature protection
32
PL Tfin module temperature too high protection
1PU DC fan A module protection
33
PU
2PU DC fan B module protection
1bH:Module 1 relay blocking or 908 chip self-check failed
34
bH
1bH:Module 2 relay blocking or 908 chip self-check failed
35
H5 Voltage too high or too low
1H9 Compressor A inverter module is not matched
36
xH9
2H9 Compressor B inverter module is not matched
37
HC High pressure sensor failure(for 75&140 model)
1HE No inset A valve error
38
HE
2HE No inset B valve error
3HE No inset C valve error
1F0 IPM module A transmission error
39
F0
2F0 IPM module B transmission error
40
F2 Superheat insufficient
Content
36
Note
The capability selection is inconsistent with the actual
model. Power on again after setting correctly
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Failure locking for 3 times in 60 minutes(Recovered by
power off or Wired controller clear fault)
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
for 3 times in 60 minutes
(Recovered by power off)
Recovered upon failure recovery
Recovered upon failure recovery
for 3 times in 60 minutes
(Recovered by power off)
Recovered upon failure recovery
Recovered upon failure recovery
for 3 times in 60 minutes
(Recovered by power off)
for 3 times in 60 minutes
(Recovered by power off)
Recovered upon error recovery
for 3 times in 60 minutes
(Recovered by power off)
Recovered upon failure recovery
Recovered upon failure recovery
Reminder code, non fault or protection
Recovered upon error recovery
for 3 times in 60 minutes(Recovered by power off)
Recovered upon error recovery
for 3 times in 60 minutes(Recovered by power off)
Recovered upon error recovery
for 3 times in 100 minutes(Recovered by power off)
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Wait at least 20min before recovering