2) Applicable standard of water quality for the unit
Table 8-7
PH value
Total hardness
Conductivity
Sulfide ion
Chloride ion
Ammonia ion
8.5.9 Installation of multi-module water system pipeline
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows.
1) Installation mode of multi-module combination water system pipeline
No.n module
No. (n-1)address
Pump
Fig.8-31 Installation of multi-module (no more than 16 modules)
Fig.8-32 Installation of multi-module (no more than 8 modules) SCV-1800EB
2) Table of diameter parameters of main inlet and outlet pipes
Table 8-8
Cooling capacity
15≤Q≤30
30<Q≤90
90<Q≤140
140<Q≤210
210<Q≤325
325<Q≤510
510<Q≤740
740<Q≤1300
1300<Q≤2080
6.8~8.0
<70ppm
<200μV/cm(25°C)
No
<50ppm
No
No.(n-1) module
No.(n-2) address
Total inlet and outlet water pipe inside nominal diameter
33
Sulfate
Silicon
Iron content
Sodium ion
Calcium ion
/
No.1 module
No.0 address
....
Drill dead hole at the position,
and move the total euent
temperature sensor at No.0
address to the position
DN40
DN50
DN65
DN80
DN100
DN125
DN150
DN200
DN250
<50ppm
<30ppm
<0.3ppm
No requirement
<50ppm
/