ABB VSN730 Product Manual page 25

System monitor
Table of Contents

Advertisement

Power consumption is typically between 2.8 VA and 3.2 VA. With load on USB bus, power
consumption is between 5.0 VA and 7.2 VA
Operating Environment
Temperature: -40°C to +85°C
Humidity:<80% storage, <85% operating (non-condensing)
Dimension
Height: 1.2" (31 mm)
Width: 5.225" (133 mm)
Length: 5.275" (134 mm)
Weight: 13 oz. (363 gm.)
Compliance
The data logger is compliant with both industrial and light industrial/commercial EMC
standards for both emission and immunity.
FCC Part 15 Class A; CISPR 22, EN 55022 Conducted and Radiated Emission; CISPR
24, EN55024 Immunity
IP Network Services
Any network connected to the logger must allow traffic to pass on the following ports. Network
firewall rules (if present) must allow responses to the logger over existing TCP connections:
Direction
Service/Port
Out
SSH/22
Out
DNS/53
Out
HTTPS/443
Out
DHCP/67,
DHCP/68
Out
NTP/123
Network Hosts
The logger will connect to the following hosts. Some servers are owned by ABB, and others are
customer or ISP servers. Servers listed as owned by "Customer IT/ISP" must be configured in the
logger using either DHCP or static network information.
Host
platform.auroravision.net
gw1.auroravision.net and/or
apt.fatspaniel.net
Site dependent
Site dependent
Protocol
Description
TCP
For remote debugging by ABB service personnel, the data logger
utilizes encrypted SSH Remote Login Protocol. To allow service
personnel remote access to the data logger, this port has to be
opened in any firewall and forwarded to the data logger. (preferred)
UDP/TCP
The data logger must be able to resolve domain names, to ensure
scalability and dynamic changes on the Internet (DNS). (required)
TCP
As an HTTP client, the data logger connects to the Aurora Vision®
Plant
communications. The logger uses this port for all services, including
data transmission, firmware upgrade, configuration management,
and remote command transmission. (required)
UDP
If DHCP service is not available, static network information must be
assigned to the logger (preferred)
UDP
The logger uses this port for network time services (NTP).
(preferred)
Purpose
Data, configuration
Logger firmware upgrade
DHCP (optional)
DNS
VSN730 System Monitor Product Manual
Management
Platform
using
Port
TCP:443
TCP:443
UDP:67, UDP:68
UDP:53, TCP:53
25 -
-
SSL/TLS
for
secure
Owner/Manager
ABB
ABB
Customer IT/ISP
Customer IT/ISP

Advertisement

Table of Contents
loading