Feature
Specification
Line voltage
3 AC 380 V ... 480 V ± 10 % up to 2000 m installation altitude. 1 AC / 3 AC 200 V ... 240 V ± 10 % up to 2000 m installation altitude.
Output voltage
3 AC 0 V ... input voltage * 0.93
Input frequency
50 Hz ... 60 Hz, ± 3 Hz
Output frequency
0 Hz ... 550 Hz, depending on the control mode
Power factor
0.7 without line reactor; 0.85 with line reactor
Inrush current
Less than rated input current
Pulse frequency (factory setting)
4 kHz. Can be increased in 2 kHz steps up to 16 kHz. Increasing the pulse frequencies leads to an output current reduction.
Electromagnetic compatibility
Interference emission: The devices are suitable for second environment category C2 in accordance with IEC61800-3 if the following
conditions are fulfilled: The motor cable is a shielded cable with low capacitance and is not longer than 50 m. The pulse frequency does
not exceed 4 kHz, the current does not exceed the LO input value. For details, refer to the Hardware Installation Manual.
Interference immunity: The devices are suitable for second environment category C3
Braking methods
DC braking, Compound braking, Dynamic braking with integrated chopper plus external Braking resistor
Environmental rating
Built in units (open type equipment): IP20,
Push through units: IP54 / UL type 12 when mounted on a flat surface of an enclosure
Motor overload protection
This equipment is capable of providing internal motor overload protection according to UL508C. The protection level is 115 %, 230 % and
400 % full load current of the equipment. This is adjusted via parameter P640 and assumes the equipment has had basic motor
commissioning for the motor used as described in the documentation.
LO Operation temperature 1)
0 °C ... 40 °C (32 °F ... 104 °F) without current derating / up to 60 °C (140 °F) with current derating
HO Operating temperature 1)
0 °C ... 50 °C (32 °F ... 122 °F) without current derating / up to 60 °C (140 °F) with current derating
Storage temperature
- 40 °C ... +70 °C (- 40 °F ... 158 °F)
Installation altitude above sea level Up to 1000 m (3300 ft) without derating / Up to 4000 m (13000 ft) with derating
Humidity
< 95% RH - non-condensing
Environmental conditions
Suitable for environmental class 3C2 according to IEC 60721-3-3 against damaging chemical substances
Pollution
For open type equipment according to pollution degree level 2. Protection against conductive pollution is required e.g. using an IP54
cabinet.
For enclosed type/Push Through equipment according pollution degree level 3.
Shock
Long-term storage in the transport packaging according to Class 1M2 of IEC 60721-3-1 : Transport in the transport packaging according to
Class 2M3 of IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
Vibration
Long-term storage in the transport packaging according to Class 1M2 to IEC 60721-3-1 : Transport in the transport packaging according to
Class 2M3 to IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
Line impedance
200 V Units: Uk
2 %, for lower values, a line reactor must be used.
400 V Units: Uk
1 %, for lower values, a line reactor must be used.
Short Circuit Current Rating
Suitable for use on a circuit capable of delivering not more than 65 kA rms symetrical amperes; 480 Vac maximum when protected by
(SCCR) 400 V units
Class J or R/C (JFHR2) semiconductor fuses only as stated
Short Circuit Current Rating
Suitable for use on a circuit capable of delivering not more than 40 kA rms symetrical amperes; 240 Vac maximum when protected by
(SCCR) 200 V units
Class J or R/C (JFHR2) semiconductor fuses only as stated
1) according to UL, operation with temperatures > 50 °C (122 °F) is not permitted at all
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the
power cables.
For United States / Canadian installations (UL/cUL): In order that the system is UL/cUL-compliant, use
UL/cUL-certified J-type fuses. Use 75° C copper wire only.
Additional requirements for Canadian compliance:
400 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 480 V
(phase to ground), 480 V (phase to phase), suitable for overvoltage category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
200 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 240 V
(phase to ground), 240 V (phase to phase), suitable for overvoltage category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
Cable lengths, using
EMI Level (Emission)
Screened cables, filtered units (class A)
50 m Second Environment, C2
Screened cables, unfiltered units,
50 m EMI Standard not fullfilled
Unscreened cables, filtered or unfiltered units
100 m EMI Standard not fullfilled
Overloads
Permissible overload for operation
Permissible overload for operation
according „Low Overload" (LO)
according „High Overload" (HO)
%
%
150 % for 3 s
200 % for 3 s
200
110 % for 57 s
150
100 % for 240 s
100
100
LO base load: 100 % LO power
HO base load: 100 % HO power
100 % LO current
t[s]
0
60
120
180
240
300
0
Compact Operating Instructions
Fitting CU to PM
Insert CU
150 % for 57 s
100 % for 240 s
100 % HO current
t[s]
60
120
180
240
300
LO values
Power
Output
current
kW
hp
A
PM240-2, Built in units, 3 AC 380 V ... 480 V
0.55
0.75
1.7
0.75
1.00
2.2
1.10
1.50
3.1
1.50
2.00
4.1
2.20
3.00
5.9
3.00
4.00
7.7
4.00
5.00
10.2
5.50
7.50
13.2
7.50
10.00
18.0
11.00
15,00
26.0
15.00
20.00
32.0
PM240-2, Push through units, 3 AC 380 V ... 480 V
3.00
4.00
7.7
7.50
10.00
18.0
15.00
20.00
32.0
PM240-2, Built in units, 1 AC/3 AC 200 V ... 240 V
0.55
0.75
3.2
0.75
1.00
4.2
1.10
1.50
6
1.50
2.00
7.4
2.20
3.00
10.4
3.00
4.00
13.6
4.00
5.00
17.5
PM240-2, Built in units, 3 AC 200 V ... 240 V
5.50
7.50
22.0
7.50
10.00
28.0
PM240-2, Push through units, 1 AC/3 AC 200 V ... 240 V
0.75
1.00
4.2
2.20
3.00
10.4
4.00
5.00
17.5
Screening methods
Line
cable
Wire
straps
Remove CU
Control cable
Braking resistor
Shielding brackets
cable
Motor cable
Declaration of Conformity
The Declaration of Conformity can be found at the following link:
http://support.automation.siemens.com/WW/view/en/30563514/134200
Power Module PM240-2, FSA, FSB, FSC
HO values
Rated
Frame
Order No. *)
(LO)
Size
Power
Output
input
current
current
kW
hp
A
A
0.37
0.50
1.3
2.3
FSA
6SL3210-1PE11-8_L1
0.55
0.75
1.7
2.9
FSA
6SL3210-1PE12-3_L1
0.75
1.00
2.2
4.1
FSA
6SL3210-1PE13-2_L1
1.10
1.50
3.1
5.5
FSA
6SL3210-1PE14-3_L1
1.50
2.00
4.1
7.7
FSA
6SL3210-1PE16-1_L1
2.20
3.00
5.9
10.1
FSA
6SL3210-1PE18-0_L1
3.00
4.00
7.7
13.3
FSB
6SL3210-1PE21-1_L0
4.00
5.00
10.2
17.2
FSB
6SL3210-1PE21-4_L0
5.50
7.50
13.2
22.2
FSB
6SL3210-1PE21-8_L0
7.50
10.00
18.0
32.6
FSC
6SL3210-1PE22-7_L0
11.00
15.00
26.0
39.9
FSC
6SL3210-1PE23-3_L0
2.20
3.00
5.9
10.1
FSA
6SL3211-1PE18-0_L1
5.50
7.50
13.2
22.2
FSB
6SL3211-1PE21-8_L0
11.00
15.00
26.0
39.9
FSC
6SL3211-1PE23-3_L0
0.37
0.50
2.3
7.5
FSA
6SL3210-1PB13-0_L0
0.55
0.75
3.2
9.6
FSA
6SL3210-1PB13-8_L0
0.75
1.00
4.2
13.5
FSB
6SL3210-1PB15-5_L0
1.10
1.50
6
18.1
FSB
6SL3210-1PB17-4_L0
1.50
2.00
7.4
24.0
FSB
6SL3210-1PB21-0_L0
2.20
3.00
10.4
35.9
FSC
6SL3210-1PB21-4_L0
3.00
4.00
13.6
43.0
FSC
6SL3210-1PB21-8_L0
4.00
5.00
17.5
29.0
FSC
6SL3210-1PC22-2_L0
5.50
7.50
22.0
37.0
FSC
6SL3210-1PC22-8_L0
0.55
0.75
3.2
9.6
FSA
6SL3211-1PB13-8_L0
1.50
2.00
7.4
24.0
FSB
6SL3211-1PB21-0_L0
3.00
4.00
13.6
43.0
FSC
6SL3211-1PB21-8_L0
*) _: A = filtered unit, U = unfiltered unit
Mains, Motor and Brake terminals
The Power Modules are fitted with detachable terminals. It can
be removed from the Power Module by pressing the release
catch. The connectors are not interchangeable.
T ightening torques:
FSA: 0.5 Nm ( 4 lbf.in)
FSB: 0.6 Nm ( 5 lbf.in)
FSC: 1.3 Nm (12 lbf.in)
Cable cross sections
2
FSA: 1.5 ... 2.5 mm
2
FSB: 1.5 ... 6 mm
2
FSA: 6
... 16 mm
Siemens AG,
Frauenauracher Str. 80,
DE-91056 Erlangen
SINAMICS G120
Line fuses
Siemens
UL, J-type
3NA3 804
(4 A)
10 A
3N A3 804
(4 A)
10 A
3N A3 801
(6 A)
15 A
3N A3 803
(10 A)
20 A
3N A3 803
(10 A)
30 A
3N A3 805
(16 A)
30 A
3NE 1814-0
(20 A)
35 A
3NE 1815-0
(25 A)
35 A
3NE 1803-0
(35 A)
35 A
3NE 1817-0
(50 A)
50 A
3NE 1817-0
(50 A)
50 A
3N A3 805
(16 A)
30 A
3NE 1803-0
(35 A)
35 A
3NE 1817-0
(50 A)
50 A
3NA3 803
(10 A)
15 A
3NA3 805
(16 A)
15 A
3NE 1814-0
(20 A)
35 A
3NE 1815-0
(25 A)
35 A
3NE 1803-0
(35 A)
35 A
3NE 1817-0
(50 A)
50 A
3NE 1818-0
(63 A)
50 A
3NE 1802-0
(40A)
50 A
3NE 1817-0
(50A)
50 A
3NA3 805
(16 A)
15 A
3NE 1803-0
(35 A)
35 A
3NE 1818-0
(63 A)
50 A
① Mains connector
② Motor connector
③ DC Link connector
④ Release catch
16 ... 14 AWG
16 ... 10 AWG
10 ... 6 AWG