Wiring Requirement - Gree GMV-ND36ZD/A-T Owner's Manual

Multi variable air conditioners, floor and ceiling type indoor unit
Hide thumbs Also See for GMV-ND36ZD/A-T:
Table of Contents

Advertisement

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit
Total Length L (m)
of Communication
Cable between
Material Type
Indoor Unit and
Indoor (Outdoor)
Light/Ordinary
polyvinyl
chloride
L≤1000m
sheathed cord.
(60227 IEC 52
/60227 IEC 53)

3.4 Wiring Requirement

Notes:
① The circuit breaker and power cord specification in above sheet are based on max
power (max current) of the unit.
② The power cord specification in above sheet is based on ambient temperature of 40°C.
③ The circuit breaker specification in above sheet is based on ambient temperature of
40°C. If the working condition is different, please adjust it according to the specification
sheet of circuit breaker.
Dimension of power cord and capacity of air switch:
Models
GMV-ND28ZD/A-T
GMV-ND36ZD/A-T
GMV-ND50ZD/A-T
GMV-ND56ZD/A-T
GMV-ND63ZD/A-T
GMV-ND71ZD/A-T
GMV-ND90ZD/A-T
GMV-ND112ZD/A-T
GMV-ND125ZD/A-T
GMV-ND140ZD/A-T
GMV-ND160ZD/A-T
Wire Size
(mm
)
2
Unit
≥2×0.75
Power Specification
220-240V-1ph-
50Hz
208-230V-1ph-
60Hz
Material
Standard
1. If the wire diameter is enlarged to
2×1 mm
communication line length can
reach 1500m.
2. The cord shall be Circular cord
(the cores shall be twisted
IEC 60227-5
together).
3. If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to
use shielded wire.
Air Switch
Minimum Sectional
Capacity
Area of Grounding
(A)
Wire(mm
6
6
6
6
6
6
6
6
6
6
6
7
Remarks
2
, the total
Minimum
Sectional Area of
)
Power Cord (mm
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
)
2