Download Print this page

echoflex TAP-21C Installation Manual page 5

Task ambient photo sensor

Advertisement

1. To enter Light Level Test mode, press and hold the teach button until the
green LED begins to blink (about 6 seconds - LEDs are located on right hand
side of the solar panel).
2. Press and hold the teach button again until the green LED stops blinking,
about 6 seconds. The green LED will start blinking faster in accordance to
the light level it is detecting, see tables below.
blinks
lux
0
< 50
1
< 142
2
< 234
3
< 326
4
< 418
5
>418
blinks
lux
0
< 50
1
< 244
2
< 438
3
< 632
4
< 826
5
> 826
The time to fully charge is based on the storage capacitor charging from a non-
operational condition. Discharge time indicates how long a fully charged sensor
will operate in the dark. The test will repeat every 2 seconds and run for a
duration of 100 seconds. You may quit the test at any time by pressing the teach
button for 6 seconds.
Range Confirmation Test: This test provides visual feedback of the sensors
signal strength by a linked receiver with range confirmation capability.
Note:
• Range Confirmation only available with "F series" Echoflex Controllers.
• The TAP must be at full charge and/or have the battery installed for Range
Confirmation Tests energy requirements.
• Only one receiver can be linked to the sensor for proper operation of the test.
• Disable repeaters in range for proper test operation.
1. To enter Range Confirmation Test mode, press and hold the teach button
until the green LED begins to blink (about 6 seconds).
2. A quick press and release of the button at this point will allow you to select
between test modes. Pressing and releasing the test button scrolls through
5
At 510 Lux (50 fc) range ( default )
foot candles time to fully charge
<5 below operating level
<14 48.0 hours
<23 26.5 hours
<33 18.0 hours
<42 13.25 hours
>42 11.0 hours
At 1024 Lux (100 fc) range (switch selectable)
foot candles time to fully charge
<5 below operating level
<24 26.0 hours
<44 12.5 hours
<63 10.0 hours
<83 9.5 hours
>83 9.0 hours
discharge time
n/a
67.0 hours
82.5 hours
86.75 hours
88.75 hours
90.0 hours
discharge time
n/a
82.5 hours
89.25 hours
90.75 hours
91.0 hours
91.25 hours