Installation
Figure 29. Low voltage wiring — D cabinet
Figure 30. Main control panel low voltage wiring
Table 7.
Recommended wire lengths
Wire Size
2
AWG
mm
22
0.33
20
0.50
18
0.75
16
1.30
30
Maximum recommended wire
length from unit controller to
sensor
Meters
Feet
0–46
0–150
47–73
151–240
74–117
241–385
118–185
386–610
Table 7.
Recommended wire lengths (continued)
Wire Size
2
AWG
mm
14
2.00
Note: The total resistance of these low voltage wires must not exceed 2.5
Ω/conductor. Any resistance greater than 2.5 Ω may cause the
control to malfunction due to an excessive voltage drop.
Maximum recommended wire
length from unit controller to
sensor
Meters
Feet
186–296
611–970
PKGP-SVX010B-EN