Trane Precedent DSJ150A Installation, Operation And Maintenance Manual page 17

Table of Contents

Advertisement

Figure 10. 12 to 25 tons duel fuel standard efficiency - gas pipe height
Note: Height of gas pipe required from inside unit base to gas shut off assembly (factory provided).
Model
DSJ (150 – 300)A
Clearances
Figure 11, p. 17
illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged unit
Figure 11.
Typical installation clearances for single and multiple unit applications
Notes:
1. When equipped with economizer
or barometric relief damper, clearance
distance is to be measured from
protruding hood instead of base.
2. Clearance is the same if any unit
.
is rotated 180
PKGP-SVX010B-EN
A
Side by Side
Note 1
7'0"
2134 MM
4'0"
1219 MM
Dimension A
inch
1 3/6
capacity, and peak operating efficiency. Providing less than
the recommended clearances may result in condenser coil
starvation, "short-circuiting" of exhaust and economizer
airflows, or recirculation of hot condenser air.
6'0"
1829 MM
Single Unit
3'0"
914 MM
5'8" With economizer/damper
1727 MM
Dimensional Data
mm
30
End to End
Note 1, 2
5'0"
1525 MM
3'0" Without economizer/damper
914 MM
17