Download Print this page

M-system R3-PD16A Instruction Manual page 5

One-shot pulse output module

Advertisement

Data Length: 8 bits
Example that ON/OFF control outputs sequentially Ch2 to Ch1 is shown below.
Example of when I/O Mode is in Output Operation (SW2-7: OFF) and ON/OFF Control channel is Not Swapped (SW2-8:
OFF).
(1) Output data Do 1 changes from 0 to 1.
(2) After Do 1's rising edge, Ch2's one-shot output turns ON for a fixed period of time (SW1's time set).
(3) After one-shot output completion, Di 2 (Ch2 output completed status) changes from 0 to 1.
(4) When Do 1 changes from 1 to 0, Di 2 changes from 1 to 0.
(5) After Do 1's sinking edge, Ch1's one-shot output turns ON for a fixed period of time (SW1's time set).
(6) After one-shot output completion, Di 1 (Ch1 output completed status) changes from 0 to 1.
Do 1
Ch1
Ch2
Di 1
(Ch1 Output Completion Status)
Di 2
(Ch2 Output Completion Status)
Note. During one shot output is on, rising edge and sinking edge are not detected.
■ CONTINUOUS OUTPUT MODE
Example of Ch1 is shown below.
Example of I/O Mode is in Output Operation. (SW2-7: OFF)
Do 1
Ch1
Di 1
(Ch1 Output Completion Status)
Note. During one shot output is on, rising edge and sinking edge are not detected.
(1)
(4)
(5) One Shot Output
(2) One Shot Output
(3) Ch2 One Shot Output Completion
(6) Ch1 One Shot Output Completion
EM-8397 Rev.1
R3-PD16A
P. 5 / 10

Advertisement

loading