INSTRUCTION MANUAL
RELAY C CONTACT OUTPUT MODULE, 4 points
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Relay contact output module ..............................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• Altitude up to 2000 meters.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
SEN TRONIC
(Modbus)
056 222 38 18
mailbox@sentronic.com
AG
MODEL
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 35mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and output signal for safety.
• Before you remove the terminal block or mount it, make
sure to turn off the power supply and output signal for
safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Be sure to close the terminal cover for safety.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
www.sentronic.com
R7M-DC4G
EM-7803-BB P. 1 / 4

Advertisement

loading

Summary of Contents for M-system R7M-DC4G-R

  • Page 1 • Locate the power input rating marked on the product and confirm its operational range as indicated below: Thank you for choosing M-System. Before use, please check 24V DC rating: 24V ±10%, approx. 35mA contents of the package you received as outlined below.
  • Page 2 R7M-DC4G COMPONENT IDENTIFICATION ■ BAUD RATE ■ FRONT VIEW Baud Rate is selected with the rotary switch. (Factory setting 0). 0: 38.4 kbps 5: 1200 bps 1 2 3 4 5 6 7 8 0 1 2 3 1: 19.2 kbps 6: 14.4 kbps CNFG.
  • Page 3 R7M-DC4G PC CONFIGURATOR The following parameter items can be set with using PC Configurator Software (model: R7CON). Refer to the users manual for the R7CON for detailed operation of the software program. ■ INTERFACE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Communication Timeout 0.0 –...
  • Page 4 R7M-DC4G ■ CONNECTION DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Y0A (NO) Y0B (NC) COM0 COM0 Y1A (NO) 24V DC Y1B (NC) COM1 COM1 Y2A (NO) Y2B (NC) COM2...