S16 INSTALLATION INSTRUCTION
1. See Receiving The Air Conditioner and Handling and Testing The Air Conditioner on page 9.
2. Using the cutout template provided with the unit, prepare the enclosure. See Figure 10 and Figure
11. The front of the unit requires a half meter clearance for proper airflow. Five centimeters is
required on each side of the unit. To avoid condensate overflow, unit must be mounted within 3° of
level.
3. Refer to mounting instructions on page 11.
4. Adjust controller to desired cabinet temperature. Refer to Displaying And Changing Program
Settings on page 16 for controller adjustment and operation.