S06 INSTALLATION INSTRUCTION
1. See Receiving The Air Conditioner and Handling and Testing The Air Conditioner on page 9.
2. Using the cutout template provided with the unit, prepare the enclosure. See Figure 7 and Figure 8.
The front of the unit requires a half meter clearance for proper airflow. Five centimeters is required
on each side of the unit. To avoid condensate overflow, unit must be mounted within 3° of level.
3. Refer to mounting instructions on page 11.
4. Adjust controller to desired cabinet temperature. Refer to Displaying And Changing Program
Settings on page 16 for controller adjustment and operation.
11.50
292
21.65
550
7.74
196
.315
8
(4)
Surface Mount
89217666
9.38
238
19.44
494
(2)
9.61
244
(2)
11.02
280
S06 300W Cutout Drawing
Dashed Lines Represent The Air Conditioner
© 2023 nVent
21.65
550
20.25
514
.315
8
(4)
Figure 7
10.44
265
10.00
254
(2)
11.02
280
Full Recess Mount
20.63
524
(2)
.19
5
- 31 -