Setting Of Save Energy And Thermistor Switch - Panasonic CS-A18BTP Service Manual

Table of Contents

Advertisement

23 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH

23.1. Energy save setting
• • • • Upper and lower limit can be set for the setting temperature
during cooling and heating operation. (The factory shipment
setting has an upper limit of 31°C and a lower limit of 16°C.)
1. While operation is stopped, press the TEMP UP and TEMP
DOWN buttons simultaneously.
2. To set an upper limit
Press the OPERATION button until HEAT is displayed.
Press the TEMP UP or TEMP DOWN button to set the
temperature.
Press the SET button to complete the upper limit setting.
Example:
If the heating display is set to 28°C, setting the temperature
to higher than 28°C will not be possible.
* Upper and lower limits cannot be set at the same time.
3. To set a lower limit
Press the OPERATION button until COOL is displayed.
Press the TEMP UP or TEMP DOWN button to set the
temperature.
Press the SET button to complete the lower limit setting.
Example:
If the cooling display is set to 22°C, setting the temperature
to lower than 22°C will not be possible.
* Press the CANCEL button to cancel the setting.
23.2. Switching to the remote
control thermistor
• • • • The temperature detection thermistor used for detecting the
indoor temperature can be switched between the thermistor
at the indoor unit and the thermistor at the remote control
unit. (The factory shipment setting is at the indoor unit side.)
1. While operation is stopped, press and hold the TEST RUN
button, TEMP UP button and TEMP DOWN button
simultaneously.
Press the FORWARD or BACK timer button to change the
temperature detection setting.
2. Press the SET button to complete the setting.
To change the setting, repeat the above operation.
52

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-a18bbp5Cu-c18bbp5

Table of Contents