Pipe Length - Panasonic CS-A18BTP Service Manual

Table of Contents

Advertisement

10 PIPE LENGTH

CORRECTION OF COOLING CAPACITY AND HEATING CAPACITIES
Correction of cooling and heating capacities according to the connecting pipe length.
The data of cooling capacities (marked on the name plate) are based on 5 meters connecting pipe and horizontal installation.
For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
REFRIGERANT ADDITIONAL CHARGE
1. Piping installation by standard piping
• • • • At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 10m.
(Refer to the following table)
But when the piping length exceeds 10m, additional charge is required according to the following table.
Example:
CU-C18BBP5
In case of 11m long pipe (one way), the amount of refrigerant to be replenished is: (11 - 10) x 20 = 20g
29