Installation Instruction; Pipe Length - Panasonic CS-F24DB4E5 Service Manual

Hide thumbs Also See for CS-F24DB4E5:
Table of Contents

Advertisement

CS-F24DB4E5 CU-L24DBE5 / CS-F28DB4E5 CU-L28DBE5

10 Installation Instruction

10.1. Pipe length

• • • • CORRECTION OF COOLING CAPACITY AND HEATING CAPACITIES
1. Correction of cooling and heating capacities according to the connecting pipe length.
The Data of cooling capacities (marked on the name plate) are based on 5 meters connecting pipe and horizontal installation.
For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
Equivalent Length = actual pipe length + number of elbow x ELE + number of oil trap x ELO
ELE : equivalent length of elbow
ELO : equivalent length of oil trap
2. For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
Outer diameter of gas side pipe
mm (inch)
12.7 (1/2)
15.88 (5/8)
19.05 (3/4)
6.35 (1/4)
34
0.20
0.25
0.35
0.18

Hide quick links: