2-23. E: A1. Discharge temperature error (Outdoor unit)

Indicator
Indoor unit
Outdoor unit main PCB
Detective actuator
Discharge temperature thermistor
Forecast of cause
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE: For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
Check point 2. Check the electronic expansion valve (EEV) and strainer
Check if EEV open.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
03-37.
Check the strainer clogging.
Check point 3. Check the outdoor unit fan and heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Check the motor. (Refer to outdoor unit fan motor in
37.)
Check point 4. Check the discharge thermistor
The discharge temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE: For the characteristics of the thermistor, refer to
03-43.
2-23. E: A1. Discharge temperature error (Outdoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
- (03-28) -
10 time flash
1 time flash
Continuous flash
Protection stop by discharge temperature ≥ 110 °C
during compressor operation generated 2 times within
24 hours.
3-way valve not opened
EEV defective, strainer clogged
Outdoor unit operation failure, foreign matter on heat
exchanger
Discharge temperature thermistor failure
Insufficient refrigerant
Main PCB failure
"Service parts information"
"Service parts information"
"Thermistor resistance values"
E: A1
on page
on page 03-
on page
2. Troubleshooting with error code