8.11 Operating Environment
Temperature range:
Temperature rate of change:
Temperature adjustment for altitude:
feet)
Relative humidity range:
Relative humidity rate of change:
8.12 Shipping And Storage In Shipment Containers For Less Than 60 Days
Temperature range:
Temperature rate of change:
Relative humidity range:
8.13 Storage In Shipment Containers For More Than 60 Days
Temperature range:
Temperature rate of change:
Relative humidity range:
Wet bulb temperature:
8.14 Altitude
Most equipment has been normally tested on a short-term basis for performance, up to an altitude of 2.4 kilometers
(8000 feet). Above this altitude, the operation of equipment may be impaired.
8.15 Airflow Rate Range
266-314 m 3 /h-kilowatts or 550-650 cfm/ton at the air-conditioner output
8.16 Vibration
Most equipment has been normally tested on a short-term basis for performance up to the vibration limits specified
below. Above these limits or with a continuous vibration level, the operation of equipment may be impaired
Frequency (Hertz)
5 - 22
22-500
21 o C +3 o C (70 o F+5 o F)
Maximum of 3 o C/hour (5.4 o F/hour)
Reduce the operating temperature by
50% RH+10% (no condensation)
Maximum of 6%/hour
-40 o to 66 o C (-40 o to 151 o F)
Maximum of 20 o C/hour (36 o F/hour)
0 to 95% RH (no condensation)
5 o to 50 o C (40 o to 122 o F)
Maximum of 11 o C/hour (20 o F/hour)
10 to 95% RH (no condensation)
Maximum of 32 o C (90 o F)
Amplitude
0.254 millimeters (0.010 inches) double amplitude
0.25 g peak
1.8 o C/1000 meters (1 o F/1000
28