YASKAWA H6R B Series Performance Test Manual page 9

Hide thumbs Also See for H6R B Series:
Table of Contents

Advertisement

Factory Set Parameters
Parameter
Value
b1-08
1
b3-01
1
b3-05
3.0
d1-01
10.0
d2-01
d2-02
E1-01
480
E1-04
E1-05
460
E2-01
H1-05
6E
H1-06
18
H1-07
6D
H2-01
0
H2-02
12
H3-03
0.0
H3-09
2
L4-05
0
L5-01
10
L5-03
5.0
o3-02
1
S5-01
1
S5-04
1
S5-05
10
S5-07
0
YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL
Table 3.2 Factory Set HV600 Bypass (Redundant Drive) Parameters
Unit
Run Command Selection in Programming Mode = Accept RUN while Programming.
Speed Search Selection at Start = Enabled
sec.
Speed Search Delay Time
Hz
Frequency Reference 1 (HAND Mode)
%
Frequency Reference Upper Limit (Must be set by user)
%
Frequency Reference Lower Limit (Must be set by user)
V
Input Voltage Setting
Hz
Maximum Output Frequency (Must be set by user)
V
Maximum Output Voltage Setting
Amps
Motor Rated Current (FLA) (Must be set by user)
Terminal Sx Function Selection = HAND Command
ON : HAND Mode
OFF : OFF Mode or AUTO Mode
Terminal Sx Function Selection = Timer Function
Terminal Sx Function Selection = AUTO Command
ON : AUTO Mode
OFF : OFF Mode or HAND Mode
Term M1-M2 Function Selection = During Run
ON : Drive is running
OFF : Drive is stopping
Term M3-M4 Function Selection = Timer Output
%
Terminal A1 Gain Setting
Terminal A2 Signal Level Selection = 4 to 20 mA
Frequency Reference Loss Detection Selection = Stop
Number of Auto-Restart Attempts
sec.
Time to Continue Making Fault Restarts (Time Between Auto Restart Attempts)
Copy Allowed Selection = Enabled
HAND Frequency Reference Selection = S5-05
HAND-OFF-AUTO Behavior = Normal
Hz
HAND Frequency Reference 1
HAND Key Function Selection = Disabled
3 Receiving and System Components