Carrier EnergyX 48HC Supplemental Installation Instructions page 52

Target national account system factory installed energy recovery 48/50hc weathermasterr commercial rooftop units 12.5 nominal ton units with puron r-410a refrigerant and i/o flex 6126 controls
Table of Contents

Advertisement

Local Access
To Communicate Through the Local Access Port
Use a computer and a USB Link Kit to communicate locally
with the I/O Flex 6126 to download or to troubleshoot.
Prerequisites
S A computer with a USB port
S A USB Link Kit
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may cause equipment
damage.
S Failure to maintain polarity while using the USB
Link on a computer that is grounded via its AC
adapter may damage the USB Link and the I/O Flex
6126 controller.
S If wary of the integrity of electrical work, and the
computer is running on AC power use a USB isolator
(secured through a third- - party manufacturer). First
plug the USB isolator into the computer's USB port,
then connect the USB Link to the isolator.
1. If using the USB Link Kit with your computer for the
first time, install the USB Link Kit's driver before
connecting the cable to the computer.
a. Put the USB Link Driver CD or WebCTRL install
DVD into the computer.
b. Install the USB Link Driver, accepting all of the
wizard's default settings.
2. Connect the USB Link Kit to the computer and to the
I/O Flex 6126 controller's Local Access port.
Connect to
computer's
USB port
Rnet Wiring Specifications
NOTE: Use the specified type of wire and cable for
maximum signal integrity.
Description
4 conductor, shielded or unshielded,
CMP , plenum rated cable
Conductor
22 AWG (7x0096) bare copper if
Rnet has only RS sensors.
18 AWG (7x0152) bare copper if
Rnet has a BACview.
Maximum length
500 feet (152 meters)
Insulation
Low--- smoke PVC (or equivalent)
Color Code
Black, White, Green, Red
Shielding
If shielded, Aluminum/Mylar shield
(100% coverage) with TC drain wire
UL temperature rating
32–167_F (0–75_C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P , or better
Connect to
the Local
Access port
USB Link Kit
C12795
Wiring an RS Room Sensor to the I/O Flex 6126
The I/O Flex 6126 supports up to 5 RS sensors on its
BACview/RS sensor port.
RS sensors can be wired to the I/O Flex 6126's Rnet port
in any of the following combinations:
S 1 RS Plus, RS Prow, or RS Pro- - F
S 1–4 RS Standards
S 1–4 RS Standards, and 1 RS Plus, RS Pro*, or RS Pro- - F
* The RS Pro is a thermistor- - based temperature sensor.
To Wire an RS Room Sensor —
1. Turn off the I/O Flex 6126's power.
2. Pull the screw terminal connector from the RS sensor.
3. Pull the screw terminal connector from the Rnet port.
4. Partially cut, then bend and pull off the outer jacket
of the Rnet cable(s). Do not nick the inner insulation.
Foil sheild
Inner insulation
.25 in.
.6 cm
5. Strip about .25 inch (.6 cm) of the inner insulation
from each wire.
6. Wire each terminal on the I/O Flex 6126's Rnet port to
the terminal of the same name on the RS room sensor.
NOTES:
If using shielded wire, connect the shield wire
S
and the ground wire to the Gnd terminal.
Maintain same polarity.
S
BACview
or
Sensor
7. Turn on the I/O Flex 6126's power.
52
Outer jacket
C12796
Rnet port
Green
Gnd
White
Rnet+
Black
Rnet−
Red
+12V
C12797