Carrier EnergyX 48HC Supplemental Installation Instructions page 11

Target national account system factory installed energy recovery 48/50hc weathermasterr commercial rooftop units 12.5 nominal ton units with puron r-410a refrigerant and i/o flex 6126 controls
Table of Contents

Advertisement

Value
Expanded Text
OAU_TYPE
Outdoor Air Unit Type
OAFANCRV
Outside Air Fan Curve
PEFANCRV
Exhaust Air Fan Curve
UNOCCRUN
OAU Unoccupied
Operation
FATALOAU
Shut Down on Fan Failure
MODWHEEL
Modulating Wheel Install
MINOACFM
Minimum Outside Air CFM
MINDCVSP
Min DCV Outside Air CFM
PEX_CTL
Power Exhaust Control
EXOFFSET
Power Exhaust CFM Offset
OAU_BPSP
Building Pressure Setpnt
OATEMPER
Outside Air Tempering
OATMPLOC
OA Tempring Lockout Temp
OATMPSPT
OA Tempring SAT Setpoint
OACFM_K
Outside Air CFM k Factor
EXCFM_K
Exhaust Air CFM k Factor
EFB_ENBL
ERV Fan Boost Enable
*
Requires an Economize which is not available for Target EnergyX units at this time.
Table 3 – Configurations - - ERV Configurations Read
Range
0=No OAU
1=ERV Module
2=Economizer*
3=Pwr Exhaust
4=OA Monitor
5=100% OA unit
6=EXv1 ERV
0 to 999
0 to 999
No/Yes
No/Yes
No/Yes
0 to 32000
0 to 32000
0=offset CFM
1=BP
---17000 to 17000
--- 0.25 to 0.25
Disable/Enable
0 to 80
35 to 80
0.8 to 1.2
0.8 to 1.2
No/Yes
Units
Default
0: no FIOP
1: FIOP EXv2
1: 04
2: 05--- 06
3: 07
4: 08--- 12
5: 14
6: 17--- 20
7: 24--- 28
1: 04, 1ph, and econ*
2: 04, 3ph, and econ*
3: 04, 1ph, and no econ*
4: 04, 3ph, and no econ*
5: 05--- 06 1ph
6: 05--- 06 3ph
7: 07
8: 08--- 12
9: 14
10: 17--- 20 and econ*
11: 17--- 20 and no econ*
12: 24--- 28
NO
YES
NO
CFM
375:
04
800:
05--- 06
1000: 07
2500: 08--- 12
3000: 14
4000: 17--- 20
5000: 24--- 28
CFM
100:
04
250:
05--- 06
600:
07
1000: 08--- 12
1500: 14--- 24
2000: 24--- 28
0
CFM
--- 200
inH
O
0.05
2
Disable
° F
60
° F
55
1.0
1.0
NO
11
Function
Defines what kind of OAU is
installed
Determine what outside air fan
curve to use
Determine what exhaust air fan
curve to use
Tells OAU to run in unoccupied
mode
Tells OAU to shut off if one of
it's fans fail
Determine if the OAU's wheel is
a modulating one
Sets Design OA CFM for
ventilation
Sets absolute minimum OA
CFM for ventilation
Determine how to control the
exhaust fans
Sets offset CFM setpoint of
exhaust based on intake
Sets required building
pressure
Determine if there is tempering
heater installed
Sets the outside temp and
below to allow tempering
Sets target Supply air
temperature during tempering
Sets outside air curve
correction factor
Sets exhaust air curve
correction factor
Tells RTU to adjust fan speed
for low outside air CFM