Carrier EnergyX 48HC Supplemental Installation Instructions page 10

Target national account system factory installed energy recovery 48/50hc weathermasterr commercial rooftop units 12.5 nominal ton units with puron r-410a refrigerant and i/o flex 6126 controls
Table of Contents

Advertisement

Value
Expanded Text
NVO_MODE
nvoUnitStatus.mode
OCCUPIED
Currently Occupied
IDFSTATE
Indoor Fan State
FANSPEED
Commanded Fan Speed
IAQ
IAQ Level (sensor)
IAQIN
IAQ Level (switch)
SAT
Supply Air Temperature
OA_TEMP
Outdoor Air Temperature
SPACE_T
Space Temperature
RETURN_T
Return Air Temperature
PE_1
Power Exhaust 1 Relay
PE_2
Power Exhaust 2 Relay
IAQANCFG
IAQ Analog Input Config
IAQANFAN
IAQ Analog Fan Config
IAQINCFG
IAQ Switch Input Config
IAQINFAN
IAQ Switch Fan Config
DAQ_LOW
AQ Differential Low
DAQ_HIGH
AQ Differential High
IAQOVPOS
IAQ Override Position
S_WHEEL
OAU Wheel Test
S_OAFAN
OAU OA Fan Speed Test
S_EXFAN
OAU PE Fan Speed Test
S_OAHEAT
OAU Tempering Heater Test
Table 2 – Inputs - - Points the ERV Read
Range
Units
xxxx
No/Yes
Off/On
xxx
%
xxxx
Low/High
xxx.x
° F
xxx.x
° F
xxx.x
° F
xxx.x
° F
Off/On
Off/On
0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0=Never
1=Occupied
2=Always
0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0=Never
1=Occupied
2=Always
0 to 5000
0 to 5000
0 to 100
%
0 to100
%
0 to100
%
0 to100
%
0 to 100
%
10
Default
Determine what mode RTU is in
Determine if RTU is occupied
Determine if the RTU indoor fan is
running
Determine if the RTU indoor fan is
running
Space CO2 sensor level (PPM)
Determine if CO2 is high or low
RTU supply air temp
RTU Outdoor Temp
Building Space Air Temp
Building Return Air Temp
N/A
N/A
0:
no FIOP
Tells if a sensor is installed for DCV or
1:
FIOP
override
0
Tells if the ERV can run during
unoccupied for high CO2
0
Tells if a switch is installed for DCV or
override
0
Tells if the ERV can run during
unoccupied for high CO2
100
Sets indoor/outdoor PPM difference to
start ventilating more
700
Sets indoor/outdoor PPM at which max
vent occurs
100
Sets OA fan speed during override
0
Test wheel while in test mode
0
Test intake fan(s) while in test mode
0
Test exhaust fan(s) while in test mode
0
Test tempering heater while in test mode
Function