HIC4xxE
Preliminary operations
Check the following upon delivery and after removal
of the packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
- 1 x motorised changeover switch
- 1 x emergency handle and fixing clip
- 1 x quickstart instruction sheet.
Accessories
• Bridging bars and connection kits.
• Terminal shrouds.
• Terminal shield.
• Voltage sensing kit.
• HZI911 interface.
• Current transformers.
Installation and commissioning
Step 1
Step 2
Cabinet/
Connecting the
Back Plate
power section
Installation
1
z Motorised source changeover switch
800A - 3200A
• Plug-in optional modules: RS485 MODBUS
communication, 2 inputs/2 outputs, Ethernet
communication, Ethernet communication +
RS485 JBUS/MODBUS gateway, Analogue
outputs, Pulse outputs.
This quick start is intended for personnel trained in
the installation and commissioning of this product.
For further details refer to the product instruction
manual available on the hager website.
• This product must always be installed and
commissioned by qualified and approved
personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables
connected to the product when voltage may be,
or may become present on the product, directly
through the mains or indirectly through external
circuits.
• Always use an appropriate voltage detection
device to confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall
in the cabinet (risk of electrical arcing).
Step 3
Step 4
COMMAND/
Power SUPPLY
CONTROL
and controller
terminal
terminal
connections
connections
Clip for
storage
of the
emergency
handle
• For 800 – 3200A (Uimp = 12kV). Terminations
must respect a minimum of 14 mm clearance
from live parts to parts intended to be earthed
and between poles.
Failure to observe good enginering practises as
well as to follow these safety instructions may
expose the user and others to serious injury or
death.
Risk of electrocution, burns or injury to
persons and/or damage to equipment.
Risk of damaging the device.
In case the product is dropped or
damaged in any way it is recommended
to replace the complete product
Step 5
Step 6
Check
Programming
.
Step 7A
AUT Mode
(Automatic
Control)
Step 7B
AUT Mode
(Remote
Control)
Step 7C
Emergency
Manual
Operation
Step 7D
Padlocking
6LE007790Aa

Advertisement

loading

Summary of Contents for hager HIC4 E Series

  • Page 1 For further details refer to the product instruction • Packaging and contents are in good condition. death. manual available on the hager website. • The product reference corresponds to the order. • This product must always be installed and • Contents should include:...
  • Page 2 Dimensions in mm 4. Power supply, sensing and control wiring 1. Installation 800A to 1600A 800A to 1000A 51,5 Use cables with 1,5 to 2,5 mm section. Screw M3 Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm ø 9 Ensure that the product is installed on a flat rigid surface.
  • Page 3 6. Programming the product Programming access Setup by Auto Configuration (Volts, Hz, Neutral pos., Ph rotation). is to be programmed powered up and after wiring verification tests. This may either be done through Press 5s the front of the ATS Controller using the keypad. Go to SETUP Scroll to...
  • Page 4: Manual Operation

    7A. Automatic operation ç è Ensure that the LED green = “Power”: LED green "AUT": ON § emergency handle is not inserted in LED Manuel/Default: the product and turn the mode " selector to the AUT é position. 7B. Automatic operation: &...
  • Page 5: Optional Modules

    The Ethernet module includes a built in Web Server for Monitoring, Engine Exerciser Control, Events... SM203: 4-20 mA SM211: modbus RS485 SM213: ethernet/modbus TCP simple SM214: gateway Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 06.21 OCOM 141942 6LE007790Aa...