Huawei LUNA2000-2.0MWH-1H0 User Manual page 151

Mart string ess
Hide thumbs Also See for LUNA2000-2.0MWH-1H0:
Table of Contents

Advertisement

LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual
Alar
Alarm
m ID
Name
3843
TCU
Communi
cation
Failure
3844
Rectifier
Communi
cation
Failure
3845
SmartMo
dule
Communi
cation
Failure
3846
CMU
Communi
cation
Failure
3851
Exhaust
Fan
Faulty
3853
ESU
Physical
Location
Failure
3856
Battery
fault
protectio
n
Issue 02 (2021-11-15)
Severit
Possible Causes
y
Minor
Cause ID=1-2
TCU communication
failed.
Minor
Cause ID=1
Rectifier communication
failed.
Minor
Cause ID=1
SmartModule
communication failed.
Minor
Cause ID=1
CMU communication
failed.
Minor
Cause ID=1 - 12
Exhaust fan is faulty.
Minor
Cause ID=1
ESU physical location
failure.
Major
Cause ID=1
Some battery modules
fail critically, causing the
system to shut down.
Cause ID=2
The temperature of some
battery modules is too
low. As a result, the
system charge limit is
exceeded.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting Suggestions
1. Check whether the communications
cable of the device is correctly
connected.
2. Check whether the power supply of
the device is normal.
3. Check whether a certificate
expiration alarm exists in the alarm
list.
1. Check whether the communications
cable of the device is correctly
connected.
2. Check whether the power supply of
the device is normal.
1. Check whether the cable connection
of the exhaust fan is correct.
2. Check whether the TCU connected
to the exhaust fan works properly.
3. Check whether the exhaust fan is
faulty. If yes, replace it.
Check whether the communications
cable of the ESU is connected properly.
Perform maintenance based on the
faulty battery module alarm and its
handling suggestions.
10 Alarm Reference
143

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Luna2000-2.0mwh-2h0

Table of Contents