Set the working mode to Scheduled charge/discharge.
Figure 8-10 Scheduled charge/discharge
Parameter
SOC Auto Calibration
Connect to Huawei NMS.
Figure 8-11 Huawei NMS
Connect to a third-party NMS.
Figure 8-12 Third-party NMS
Connect to third-party devices.
Copyright © Huawei Technologies Co., Ltd.
8 SmartLogger Web-based Deployment
Description
▪
Enable:Automatic SOC calibration is
enabled. If the total charge and discharge
energy reaches the threshold or the
calibration function has not been
triggered for 30 days, the SOC automatic
calibration is performed. The SOC
automatic calibration is performed in
battery racks. During calibration, the cut-
off SOC settings will be ineffective.
▪
Disable:Automatic SOC calibration is
disabled.