Safety Information

WARNING
To insure safe and proper operation of your equipment, it is critical to read and adhere to
all of the following safety warnings and precautions. Improper installation or use of this
product can cause serious bodily injury or death!
WARNING
This product should not be used to transfer fluids into any type of aircraft.
WARNING
This product is not suited for use with fluids intended for human consumption or fluids
containing water.

Pad Locking

Your Fill-Rite pump nozzle can be locked for added security. With
the pump turned off, and the nozzle in the stored position, a pad
lock can be inserted through the nozzle rest and the nozzle handle
opening. This configuration prevents the nozzle from being removed
and the pump being turned on.

Installation

FR902 Series remote dispensers and tank top pumps must be installed in accordance with local, state, and
national electrical code NEC/ANSI/NFPA 70, NFPA 30, NFPA 30A, and NFPA 395, on a fixed, above ground tank not
accessible to the public.
In FR902RU and FR902LRU installations, a UL listed emergency shut-off valve with fusible link must be installed
at the dispenser inlet. All piping must be Schedule 40. Use UL classified gasoline and oil resistant pipe compound
on all threaded joints. See page 12 for sample plumbing diagram. For use ONLY with UL Listed Interchangeable
(automatic or manual) Service Station Type Hose Nozzle Valves or Non-Interchangeable Service Station Type Nozzle
Valves Model Catlow MAX 1, Husky 3N1-GS, and Husky 1+V111.
Additionally, FR902RU and FR902LRU Dispensers require a UL listed pressure relief valve be incorporated into the
installation, either as part of the pump or separately at the dispenser itself.
fillrite.com
| 902V SERIES CABINET DISPENSER
1. NEVER smoke near the meter, or use the meter near open flames when metering a
flammable liquid! Fire can result!
2. A "Fill-Rite" Filter should be used on the meter outlet to insure no foreign material is
transferred to the fuel tank.
3. Threaded pipe joints and connections should be sealed with the appropriate sealant
or sealant tape to minimize the possibility of leaks.
4. Storage tanks should be securely anchored to prevent shifting or tipping when
full or empty.
5. To minimize static electricity build up, use only static wire conductive hose when
metering flammable fluids, and keep the fill nozzle in contact with the container
being filled during the filling process.
6. DO NOT exceed 50 psi/ 3.5 BARS line pressure.
7. DO NOT install additional foot valve or check valve without a pressure relief valve;
cracking may result.
INSTALLATION AND OPERATION MANUAL