Power-On Commissioning
1. Before powering on the UPS5000, ensure that the check items in the
Service Report
and the post-installation check items are verified.
2. Measure the voltage and frequency of the UPS upstream input switch. The line voltage
range is 138–485 V AC, and the frequency range is 40–70 Hz.
Powering On the UPS
5.1
To turn on a switch, insert the switch handle in place, and then rotate
the handle.
After turning on the switch, ensure that the triangle arrow on the
flange points to ON.
Switch handle placed on the tray of the front
door. Four switches share one handle. Remove
the handle before operating different switches
and reinstall it after the operations are complete.
If desiccant is available inside the cabinets, remove the desiccant.
Turn on the upstream bypass and mains input switches.
Turn on the UPS bypass input switch, mains input switch, and output switch.
After the UPS is powered on, initialization begins. The monitoring display unit (MDU)
displays the initialization progress bar.
Initial Startup
5.2
1. Obtain the startup password through the app. After the application is approved, enter the
password on the service authorization screen of the device to complete device authorization.
Technical support engineers can obtain the service authorization code through the app. For
details, see the
Data Center Facility Deployment Guide
.
UPS5000-H-(400 kVA-600 kVA)-FT Quick Guide (100 kVA Power Modules)
2. Set the language, time, date, network parameters, and system parameters on the Settings
Wizard screen.
UPS5000 Startup
Set all battery parameters according to the actual situation: Assume that the battery
specifications are 150 Ah/12 V, 40 batteries are connected in series, and two battery strings
are connected to the UPS in parallel. Set Single battery voltage(V) to 12, Single battery
capacity(Ah) to 150, Battery in a battery string to 40, and Number of battery strings to 2.
3. After you perform the settings, the Bypass mode and No battery alarms are reported by the
MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
4. If the system has connected to the remote EPO switch, you need to choose Monitoring > UPS
System > Running Parameter > System Settings on the WebUI and set EPO detection to
Enable.
5. View the system running status diagram on the MDU to check that the UPS is working in
bypass mode.
Starting the Inverter
5.3
1. On the main menu, choose Common Functions and tap Inv. ON.
2. In the displayed login window, enter the user name and password, and tap
3. In the displayed dialog box, tap Yes to start the inverter.
System User
admin (system administrator)
operator (common user)
.
LCD Preset
WebUI Preset
To ensure system security,
Password
Password
change the LCD and
000001
Changeme
WebUI passwords after
000001
Changeme
the first login.
3
5.4
Powering On Loads
1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears
from the MDU.
2. After confirming that the battery strings are properly connected, turn on the battery string
input circuit breaker. If there are multiple battery strings, turn on the circuit breaker for each
battery string and then turn on the general circuit breaker between battery strings and the
UPS. The No battery alarm disappears from the MDU.
3. Turn on the UPS downstream output switch to supply power to the loads.
5.5
(Optional) Setting Parameters for the BCB Box
If a BCB box is configured, set MUE05A connection to Enable in System Info > Settings > Dry
Contacts Set, and then set BCB connection [OL] and Battery breaker [STA] to Enable.
06
Shutting Down the UPS
Shutting Down the Inverter to Transfer the UPS to Bypass Mode
6.1
After you shut down the inverter, the UPS transfers to bypass mode if the bypass is normal;
the UPS supplies no power if the bypass is abnormal. Before shutting down the UPS, ensure
that all loads have been shut down.
1. On the main menu of the LCD, choose Common Functions and tap Inv. OFF.
2. In the displayed login window, enter the user name and password, and tap
3. In the displayed dialog box, tap Yes to shut down the inverter.
6.2
Powering Off a Single UPS
To turn off a switch, insert the switch handle in place, and then rotate the
handle.
After turning off the switch, ensure that the triangle arrow on the flange
points to OFF.
Turn off the downstream output switch.
Turn off the battery string circuit breaker. If there are multiple battery strings, turn
off the general circuit breaker between battery strings and the UPS and then
turn off the circuit breaker for each battery string.
Turn off the UPS mains input switch, bypass input switch, and output switch.
Turn off the upstream mains and bypass input switches.