CornellCookson AlarmGard FST-EPBD Series Installation Instructions And Operation Manual

Fire door operator

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
AND
OPERATION MANUAL
AlarmGard
®
Fire Door Operator
FST-1511EPBD / FST-5011EPBD
FST-EPBD Series
Multiple Motors

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AlarmGard FST-EPBD Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for CornellCookson AlarmGard FST-EPBD Series

  • Page 1 INSTALLATION INSTRUCTIONS OPERATION MANUAL AlarmGard ® Fire Door Operator FST-1511EPBD / FST-5011EPBD FST-EPBD Series Multiple Motors...
  • Page 2: Important Installation Instructions

    IMPORTANT INSTALLATION INSTRUCTIONS WARNING –To reduce the risk of death or serious injury to persons: READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications.
  • Page 3: System Description

    13. Locate the control station: (a) within sight of the door, and (b) at a minimum height of 5 feet above floors, landings, steps, or any other adjacent walking surface and (c) away from all moving parts of the door. 14.
  • Page 4: Specifications

    SPECIFICATIONS MOTOR Type: Restricted cycle duty (10 cycles per hour) Rating: FST-1511: 50 ft.lb/sec per motor, FST-5011: 150 ft.lb/sec per motor Speed: 1560 RPM Voltage: 115V, 1 phase Current: See motor nameplate ELECTRICAL Transformer: 24VAC Wiring Type: Momentary pressure open, stop, constant pressure close (provided standard), with provision for momentary pressure close* Limit Adjustment: Linear driven, fully adjustable screw type cams.
  • Page 5: Installation Instructions

    INSTALLATION INSTRUCTIONS Consult door manufacturer for install details. INSTALLATION POSITIONS NOTE: Any change in mounting position may result in a change of operator rotation and consequently in a change of control functions. Consult factory for any changes. (LS mounting position is LH operator, RS position is RH operator) FST-EPBD Series REVISION # 0004 DATE: 04/01/2021...
  • Page 6: Operator Mounting

    OPERATOR MOUNTING MOTOR MOUNTING TO DOOR PIPE 1. Door pipe and mounting holes preparation. (Pipe is not provided with the operator.) Drilling 4 - 15/64” Drilling 4 - 15/64” Drilling Drilling 8 - 7/64" x 82° 8-7/64"x82° Drilling Area for Drive Flange Drilling Area for Drive Flange (Figure 1 for FST-1511) (Figure 2 for FST-5011)
  • Page 7 MOTOR MOUNTING TO BRACKET 1. Dismantle the limit switch mechanism before mounting on the bracket if required. 2. Make sure the layout of the mounting holes on the bracket is correct. 3. Mount the operator to the mounting plate. 4. Mounting the limit switch mechanism on operator by fastening screws x 6. (Figure 5 for FST-1511) (Figure 6 for FST-5011) FST-EPBD Series...
  • Page 8: Limit Switch Adjustment

    LIMIT SWITCH ADJUSTMENT Make sure the limit cams are positioned between the limit switch actuators before proceeding with adjustments. 1. Open / remove the control panel cover. 2. Open or close door to determine the moving direction of the limit switch cams. 3.
  • Page 9: Wiring Instructions

    WIRING INSTRUCTIONS Disconnect power at the fuse box before proceeding with any wiring. WARNING ELECTRICAL CONNECTIONS – Installation of all wiring and connections shall be performed in accordance with, but not limited to, the latest NFPA, NEC and CEC standards. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material, wiring gauge related to power capacity requirements and circuit length and wiring methods.
  • Page 10 MOTOR WIRING FST-1511EPBD 1. Two (2) motors can be connected on one (1) power PC board. 2. See wiring diagrams for power PC boards wiring details. Motors connections routing, illustration only. Consult factory for details. MOTOR 2 MOTOR 1 Motors connections on power PC boards, illustration only. Consult factory for details. FST-EPBD Series REVISION # 0004 DATE: 04/01/2021...
  • Page 11 FST-5011EPBD 1. One (1) motor can be connected on one (1) power PC board. 2. Two (2) power PC boards can be mounted in FST-5011EPBD control panel. 3. See wiring diagrams for power PC boards wiring details. Motors connections routing, illustration only. Consult factory for details. MOTOR 2 MOTOR 1 Motors connections on power PC boards, illustration only.
  • Page 12: Control Wiring

    CONTROL WIRING If the door is not visible from the control station, or if any device other than the control station is used to activate the door, an entrapment protection device must be installed on the door. Failure to install an entrapment WARNING protection device may result in serious injury or death to person(s) trapped beneath the door.
  • Page 13 Disconnect power at the fuse box before proceeding with any wiring. WARNING 2. Locate the control station where the user can clearly see the operation of the door. Mount the enclosed placard adjacent or near the door. Controls shall be far enough from the door, or positioned such that the user is prevented from coming in contact with door while operating the WARNING controls.
  • Page 14: Control Function

    A. Control Function: A. A. During Alarm S.E. Reverse 0 Cycle S.E. Reverse 1 Cycle S.E. Reverse 3 Cycles A-2. A-2. EDGE OP. L CN26: Multi-function socket for optional module M.CL M.OP PHOTO REV 5S A.DLY F.DLY A.OPEN Momentary Pressure Open Open Constant Pressure...
  • Page 15: Auxiliary Function

    B. Auxiliary Function: B-2. Radio control 24VAC Push button 24VAC B-1. OPEN Open door CLOSE STOP OP EN CLOSE OPEN S TOP Close door CLOSE STOP OPEN Stop door CLOSE STOP *FST-1511EPBD is shown as above, FST-5011EPBD unit is similar. FST-EPBD Series REVISION # 0004 DATE: 04/01/2021...
  • Page 16: Timer Instruction

    C. Timer Instruction: C-1. Decrease time. I ncrease time. Timer 2 setup. Timer 1 setup. *FST-1511EPBD is shown as above, FST-5011EPBD unit is similar. (1) Timer 1 – Mid-open timer: Timer starts counting when door leaves close limit. Door stops after opening for set time.
  • Page 17 (3) To Set Timer 1 (Mid-open Timer):  Press and hold for 5 seconds. Display will flash.  to increase or to decrease time.  Press to save setting. Without pressing, no adjustment is saved. Mid-Open Timer Set the Max. 99 Sec desired time.
  • Page 18: Lcd Display Instruction

    D. LCD Display Instruction: Display Status Display Status T1 setting Door closing T2 setting Door opening T1 or T2 setting Alarm condition completed Limit switches don't Limit switches don't response or respond both response or respond both limits reached in standby limits reached in startup or running period.
  • Page 19: Sound Warnings

    F. Sound Warnings: Item Description Sound Alarm warning signal B____, B____, B____, B____, … Terminal CN2 (1,4) not connected B.B.B.B., B.B.B.B., B.B.B.B., B.B.B.B., … AC power abnormal B____ B.B., B____ B.B., B____ B.B., ….. Battery voltage below 21.5V B. B. B. B. B. B. B. B. B. B. ….. Battery failed B___B.B.B., B___B.B.B., B___ B.B.B., ...
  • Page 20 FST-EPBD Series REVISION # 0004 DATE: 04/01/2021...