INSTALLATION INSTRUCTIONS
AND
OPERATION MANUAL
FSNX-150EP Series
(v2)
NEMA 4X
Rolling Fire Door Operators
UL325-2010 Compliant
Restricted Duty Operators
SMART Control

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FSNX-150EP Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for CornellCookson FSNX-150EP Series

  • Page 1 INSTALLATION INSTRUCTIONS OPERATION MANUAL FSNX-150EP Series (v2) NEMA 4X Rolling Fire Door Operators UL325-2010 Compliant Restricted Duty Operators SMART Control...
  • Page 2: Table Of Contents

    APPENDIX 2: Control Connections Diagrams ................31 APPENDIX 3: Control Connections Diagrams ................32 APPENDIX 4: External Timer Defeat Switch Connection .............. 33 APPENDIX 5: Wiring Change Instruction from 230V to 208V 3 Phase Operator ......34 FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 3: Important Installation Instructions

    13. Any change in mounting position may result in a change of operator rotation and consequently in a change of control functions. Consult factory for any changes. 14. For products having a manual release, instruct the end user on the operation of the manual release. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 4: Specifications

    1. Non-contact device (photo eye) can be used on doors up to 45 ft. wide (or maximum rated range of device if less than 45 ft.). Use a sensing edge to provide entrapment protection on doors over 45 ft. wide. 2. Sensing edge can be used on all doors. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 5: Types And Sizes Of Doors

    Consult factory for any changes. (LS and RA mounting positions are LH operators, RS and LA positions are RH operators) Consult factory for changes in mounting positions. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 6: Operator Mounting

    (See figure - T1, T2 location) 2. Once the drive chain has been tightened and the base leg screws have been set, and then tighten the operator set screws. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 7: Wiring Instructions

    Unless the operator includes an internal lock sensing system, or external electrical interlocks are installed, remove or make all door locks inoperative, or secure locks in the unlocked position. Failure to disable the locks could result in damage to the door or operator. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 8: Control Wiring

    Failure to do so may result in serious injury or death to person(s) trapped beneath the door.  Changing from left hand to right hand or vice versa could result in change of control wiring. Consult factory for details. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 9: Entrapment Devices Wiring

    Please refer to sensing device manufacturer for specific installation and maintenance requirements. 2. After installation, be sure that the operator, controls, and sensing edge or other entrapment protection devices have been tested and function properly. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 10: Input Power Connections

    INPUT POWER CONNECTIONS Single-phase power source See operator plate for correct voltage. A-3. Three-phase power source See operator plate for correct A-3. voltage. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 11: Limit Switch Adjustment

    7. Micro switch (A or B) can be adjusted to accommodate sensing edge cut-off position. NOTE: “C” is usually the open limit switch and “D” is usually the close limit switch. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 12: Control Settings

    24VDC 11&12 Alarm attempting to close the number of times selected on MAX 0.5A Connection Non-Monitored the S4 switch N/C Dry Contact Sensing Devices (N.O. Dry Contact) FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 13: Auxiliary Function

    AUXILIARY FUNCTION 24VAC Push button B-2. Radio control Radio control B-1. B-1. STOP CLOSE Open door Open door OPEN Close door Close door STOP CLOSE OPEN Stop door Stop door STOP CLOSE OPEN FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 14: Timer Instruction

    Pressing open again at mid-open position will cause door to open limit. Time 2 – Close timer : Timer is active when door stops and is not at close limit. 2. Standard Mode: Cycle counter FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 15: Lcd Display Instruction

    Min. 1 Sec Min. 1 Sec LCD DISPLAY INSTRUCTION Display Status Display Status T1 setting Door closing T2 setting Door opening T1 or T2 setting Alarm condition completed FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 16: Light Indication

    OFF: Not activated. OFF: Not activated. ON: Power ON. OFF: Power OFF. SOUND WARNINGS Item Description Sound Alarm warning signal B_____ B_____ B_____ B_____ …… Terminal CN2 (1,4) not connected B.B.B.B. B.B.B.B. B.B.B.B. …. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 17: Wiring Diagrams

    WIRING DIAGRAMS INPUT POWER 115V 1 PHASE OPEN CLOSE STOP FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 18 STOP CLOSE OPEN INPUT POWER 115V 1 PHASE FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 19 INPUT POWER 230V 1 PHASE OPEN CLOSE STOP FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 20 STOP CLOSE OPEN INPUT POWER 230V 1 PHASE FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 21 NOTE : ˙ ˙ INPUT POWER 208V / 230V 3 PHASE OPEN CLOSE STOP FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 22 STOP CLOSE OPEN INPUT POWER 208V / 230V 3 PHASE NOTE : ˙ ˙ FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 23 INPUT POWER 460V 3 PHASE OPEN CLOSE STOP FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 24 STOP CLOSE OPEN INPUT POWER 460V 3 PHASE FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 25 INPUT POWER 575V 3 PHASE OPEN CLOSE STOP FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 26 STOP CLOSE OPEN INPUT POWER 575V 3 PHASE FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 27: Important Safety Instructions

    6. KEEP DOORS PROPERLY OPERATING AND BALANCED. See Door Manufacturer’s Owner’s Manual. An improperly operating or balanced door could cause severe injury or death. Have trained door systems technician make repairs to cables, spring assemblies, and other hardware. SAVE THESE INSTRUCTIONS. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 28: Fusible Link Connections

    NFPA-80 and the authority having jurisdiction for fusible link location(s) and method. Fusible link connection location. Fusible link connection hole. Remove cotter pin after installation. * Illustration only, not drawn to scale. See product for actual details. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 29: Testing

    “CLOSE” button or key switch position does not cause the door to stop, this condition must be corrected immediately. Improper operation could result in serious injury or death to person(s) trapped beneath the door. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 30: Maintenance Instructions

    WARNING Do not place hands or tools in or near the operator when the power is connected or when testing control or sensing devices. Always disconnect power before servicing or adjusting the operator. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 31: Appendix 1: Multiple Sensing Devices Connection Instruction

    Primary Sensing Device Connection Part No: GDAXX-0AMA-X001 Part No: GDAXX-0AMA-X001 OR Harness Part No: ADAWE-PDL0-0002 Parallel connection AND Harness Part No: ADAWE-PDL0-0001 Serial connection Secondary and Third Sensing Devices connect on 1st and 2nd sensing modules. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 32: Appendix 2: Control Connections Diagrams

    Please Remove Please Remove Jump Pin First Jump Pin First "A" "A" OPEN OPEN OPEN CLOSE CLOSE CLOSE "A" "A" Remove Remove Jump pin Jump pin KEY REQUIRED TO REMOVE COVER STOP STOP FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 33: Appendix 3: Control Connections Diagrams

    With and without key lockout KEY LOCKOUT 3-2 BUTTON STOP STOP OPEN OPEN OPEN OPEN OPEN Key switch OPEN CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE STOP STOP STOP STOP Ceiling Pull Switch Station JUMP CLOSE/OPEN RADIO CLOSE/OPEN FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 34: Appendix 4: External Timer Defeat Switch Connection

    APPENDIX 4: External Timer Defeat Switch Connection FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...
  • Page 35: Appendix 5: Wiring Change Instruction From 230V To 208V 3 Phase Operator

    "230V" wire connector. connector. Plug the yellow "208V" wire connector into the red "PWR" wire Remove the insulating cap from the yellow "208V" wire connector. connector. 3. Completed. FSNX-150EP Series REVISION # 0000 DATE: 06/08/2022...