9. Module parameter table (CR code means the corresponding Modbus register address)
Note: CR code is corresponding to the Modbus register address.
CR code(Hex)
communicatio
n address
Low byte for Module code, Higher 3-bit of the High-Byte is ID
00H
number. Lower 5-bit of High-Byte is version number.
01H
Communication Address
Communication Protocol
Low byte lower 4-bit:0 - N,8, 2 For RTU
2 - O 8, ,1 For RTU
3 - N,7, 2 For ASCII
4 - E,7, 1 For ASCII
5 - O,7, 1 For ASCII
02H
Low byte higher 4-bit:0 – 2400
03H
Module name
04H
Module name
05H
Module name
06H
Module name
07H
IP Address: default 192.168.1.111
08H
IP Address: default 192.168.1.111
09H
Month/date
0AH
Year batch number
High byte subnet mask( b3~b0,"1" means 255, "0" means 0, for
0BH
example subnet mask 255.255.255.0 b3~b0=1110), low byte
manufacturer code HW
0CH
Verification code
0DH
Serial number low byte
0EH
Serial number high byte
Error Code
0:normal
1: illegal firmware identity
0FH
2: firmware incomplete
3:system data access exception
4: No external 24V power supply
10H
Channel 1 average weight
Channel 1 status code
bit0:No-load( zero point weight)
bit1:exceed the upper limit of weight
11H
bit2:measurement value stable
bit3~15:reserve
12H
Channel 1 real-time weight
Channel 1 uses 32-bit display flags:
13H
0: 16-bit weight display
1: 32-bit weight display
Channel 1 Real-time Weight 32 Bit Value:
14H~15H
14H: 32-bit low byte
Function description
1 - E,8, 1 For RTU
6 - N,8, 1 For RTU
1 - 4800
2 - 9600
3 - 19200
4 - 38400
5 – 57600
6 - 115200
Second generation module terminal:
Property
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R/W
R
R
R
R
R
R
R
R/W32
R
5 / 24
Haiwell PLC -- Load Cell Module User Manual
Factory
Remarks
default
xxxx
1
Range:1~247
48
(19200, N,8,
2 RTU)
0x016F
0xC0A8
Low byte code cannot be
modified
0
0