10. Module Parameter Table

4-channel analog module parameter table

Note: CR code is corresponding to the Modbus register address, the ray parts are read-only ,the white parts are readable and
writable.
CR code
00H
Low byte for module code, and high byte for module version number.
01H
Communication address
Communication protocol: The low 4-bit of the low byte: 0 - N,8,2 For RTU, 1 - E,8,1 For RTU, 2 - O,8,1 For RTU, 3 - N,7,2 For ASCII, 4 -
02H
E,7,1 For ASCII, 5 - O,7,1 For ASCII, 6 - N,8, 1 For RTU
The high 4-bit of the low byte: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 - 115200
03H~06H
Module name
07H~08H
Default IP address: 192.168.1.111
09~0AH
Reserve
0BH
High byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example subnet mask 255.255.255.0, b3~b0=1110), low byte reserved
0CH-0EH
Reserve
Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power
0FH
supply
10H
channel 1 input value
11H
channel 2 input value
12H
channel 3 input value
13H
channel 4 input value
14H
channel 1 signal type, note 2
15H
channel 2 signal type, note 2
16H
channel 3 signal type, note 2
17H
channel 4 signal type, note 2
18H
Use the engineering value mark, note 6
channel 1 engineering lower limiting
19H
value
channel 2 engineering lower limiting
1AH
value
channel 3 engineering lower limiting
1BH
value
channel 4 engineering lower limiting
1CH
value
channel 1 engineering upper limiting
1DH
value
channel 2 engineering upper limiting
1EH
value
channel 3 engineering upper limiting
1FH
value
channel 4 engineering upper limiting
20H
value
21H
channel 1 sampling frequency, note 1
22H
channel 2 sampling frequency, note 1
23H
channel 3 sampling frequency, note 1
24H
Channel 4 sampling frequency, note 1
25H
channel 1 zero point correction value
26H
channel 2 zero point correction value
27H
channel 3 zero point correction value
28H
channel 4 zero point correction value
Channel 1~4 input disconnection
29H
alarm, note 5
2AH
Reserve
2BH~2FH
8-channel analog module parameter table
Note: CR code is corresponding to the Modbus register address, the gray parts are read-only, the white parts are readable and
writable.
CR code
00H
Low byte for module code, and high byte for module version number.
01H
Communication address
Communication protocol: The low 4-bit of the low byte: 0 - N,8,2 For RTU, 1 - E,8,1 For RTU, 2 - O,8,1 For RTU, 3 - N,7,2 For ASCII, 4 -
02H
E,7,1 For ASCII, 5 - O,7,1 For ASCII, 6 - N,8, 1 For RTU
The high 4-bit of the low bytes: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 - 115200
03H~06H
Module name
07H~08H
Default IP address: 192.168.1.111
09~0AH
Reserve
0BH
High byte subnet mask(b3~b0,1 indicates 255,0 indicates 0 , for example, subnet mask 255.255.255.0, b3~b0=1110), low byte Reserved
0CH~0EH
Reserve
Error code: 0-Normal, 1-Illegally firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power
0FH
supply
10H
channel 1 input value
(CR code is corresponding to the Modbus register address)
S04AI
channel 1 output value
channel 2 output value
channel 3 output value
channel 4 output value
channel 1 signal type, note 2
channel 2 signal type, note 2
channel 3 signal type, note 2
channel 4 signal type, note 2
Use the engineering value mark, note 6
channel 1 engineering lower limiting
value
channel 2 engineering lower limiting
value
channel 3 engineering lower limiting
value
channel 4 engineering lower limiting
value
channel 1 engineering upper limiting
value
channel 2 engineering upper limiting
value
channel 3 engineering upper limiting
value
channel 4 engineering upper limiting
value
power-off output mark, note 8
channel 1 power-off output value
channel 2 power-off output value
channel 3 power-off output value
channel 4 power-off output value
Channel indicator status, note 7
Reserve
S08AI
channel 1 output value
Function description
S04AO
input channel 1 input value
input channel 2 input value
input channel 1 signal type, note 2
input channel 2 signal type, note 2
Use the engineering value mark, note 6
input channel 1 engineering lower limiting value
input channel 2 engineering lower limiting value
input channel 1 engineering upper limiting value
input channel 2 engineering upper limiting value
input channel 1 sampling frequency, note 1
input channel 2 sampling frequency, note 1
input channel 1 zero point correction value
input channel 2 zero point correction value
Channel 1~2 input disconnection alarm, note 5
output channel 1 output value
output channel 2 output value
output channel 1 signal type, note 2
output channel 2 signal type, note 2
Use the engineering value mark, note 6
output channel 1 engineering lower limiting value
output channel 2 engineering lower limiting value
output channel 1 engineering upper limiting value
output channel 2 engineering upper limiting value
power-off output mark, note 8
output channel 1 power-off output value
output channel 2 power-off output value
output channel indicator, note 7
Reserve
Function description
S08AO
input channel 1 input value
6 / 18