Advertisement
This product is manufactured in accordance with standards EN 60730-2-9, EN 60730-2-7, ETSI EN 301 489-1 (DPT R, DPT VR), ETSI EN 300 200-2 (DPT R, DPT VR), in accordance with applicable EC directives and it is entirely manufactured in Italy.
![]() | Power supply: Batteries (2x1,5V) - Output: relay ON-OFF |
![]() | Power supply: 230Vac, 50Hz - Output: relay ON-OFF |
![]() | Power supply: Batteries (2x1,5V) - Output: Radio 868.2 Mhz |
![]() | Power supply: 230Vac, 50Hz - Output: Radio 868.2 Mhz |
![]() | Power supply: 2x1.5V LR03 Alkaline batteries (AAA type) |
![]() | Battery life > 1 year |
![]() | Power supply: 230Vac, 50Hz |
![]() | Maximum power absorbed: < 0.5W Maintenance of clock in the absence of supply voltage >12h |
![]() | Maximum capacity of the contacts: 5A(1A) 250VAC |
![]() | Type of action: 1B |
![]() | Operating frequency: 868.2 Mhz |
![]() | Category of the receiver: 2 Duty cycle of the transmitter < 1% Capacity: 300 m outdoors, 20 m indoors Type of antenna: internal, on PCB |
Class ErP I (+1%) - EU 811/2013
Maximum ambient temperature: 50°C
Temperature display range: 0°C÷39°C
Temperature regulation range: 5°C÷35°C
Temperature resolution: 0.1°C
Temperature differential: from 0.1°C to 2.0°C (standard 0.2°C)
Temperature probe: NTC 100KΩ@25°C
Degree of protection: IP20
Insulation class: Type II (double insulation)
Pollution degree: 2
Software: class A
Heat and fire resistance: Category D
Storage temperature: -25÷60°C
Rated impulse withstand voltage: 2.5kV
Installation: wall-mounting
It is recommended to install the device in strict accordance with the safety regulations and laws in force. Before making any connection, make sure that the main switch is off.
Install the device away from heat sources and drafts, about 1.5m from the floor.
Open the device by pressing the small tab on the underside of the base (Fig.1 A). Turn the front panel upwards (Fig.1 B) and lift it slightly to release it (Fig.1 C).
Attach the base to the wall, using the horizontal (Fig.2 A-A) or diagonal distance (Fig.2 B-B).
Remove the internal protection covering the terminals by unscrewing the screw (Fig.2 C) and turning the cover upwards. Attach the base to the wall, using the horizontal (Fig.2 A-A) or diagonal distance (Fig.2 B-B). Insert the cables through the opening at the bottom and connect them to the terminal board (Fig.4) then replace the internal cover and tighten the screw (Fig.2 C).
Insert the batteries in the front panel (Fig.3).
To close the device, proceed as before but reversing the sequence of operations: match the upper sides of the two parts (Fig.1 C) then turn the front panel downwards (Fig.1 B) until the lower hook clicks (Fig.1 A) on the base.
When the symbol flashes (batteries low) it is necessary to replace them. Proceed as indicated in the installation instructions (Fig. 1 and Fig.3). Put the cover back on the base before performing any operation.
The controls consist of a ring with four positions identified by the arrows ◄ ►▲▼ with a central button OK. Press the ring in correspondence with the arrow to activate one button at a time. Press the OK button in the centre. Use the arrow buttons to change the time and temperature values or to select the options, the central OK button usually confirms the settings.
Set the clock
Pair with the radio receiver RCV by means of the "rAd" parameter in the installer menu. The procedure is performed at the factory but it is possible to repeat it (for example when a device is replaced).
First prepare the receiver RCV by following the instructions.
The antifreeze function is active. Press for 3 seconds:
▼ to set the clock (as above).
▲ to set the season mode Summer/Winter (standard: WINTER).
◄ to go from OFF to ON and vice versa. Press OK for 10 seconds to enter the Installer Menu.
Ambient temperature is always in the foreground.
Press OK to show the clock or the set-point temperature in the upper right corner.
Press ► to select AUTO, MAN, MAN ECO modes (standard: AUTO).
(Fig.7)
Press ▲ or ▼ to change and save the temperature set-points.
MAN = comfort temperature (standard: WINTER = 20,0°C / SUMMER = 25,0°C).
MAN ECO = economy temperature (standard: WINTER = 16,0°C / SUMMER = 28,0°C).
(Fig.8 and Fig.9)
The display shows in its lower part:
The set-point temperature (t1 or t2) depends on the saved time program and changes automatically.
Hold ▼ 3 seconds, the current time of day appears in the upper righ corner
SET and the symbol █ related to the current time flash.
Select the desired temperature per every hour along the day.
Press ▲ to set t1 temperature.
Press ▼ to set t2 temperature.
Press ◄ ► to move along the hours without changing the settings.
Press OK to confirm the program settings.
The display shows t1 (Comfort) temperature first and t2 (Economy) soon after
Change t1 (Comfort) by ▲▼ then OK
(standard: WINTER = 20,0°C / SUMMER = 25,0°C).
Change t2 (Economy) by ▲▼ then OK
(standard: WINTER = 16,0°C / SUMMER = 28,0°C).
The Comfort temperature is higher than the Economy temperature (t1>t2). When Tamb < Tset (Room temperature < Set temperature), the heating is activated .
The Comfort temperature is lower than the Economy temperature (t1<t2). When Tamb > Tset (Room temperature > Set temperature), the cooling is activated .
Normally, the display shows the symbol fixed (Fig.7 e Fig.9). If
flashes, check the devices, try to repeat the pairing procedure or change its position.
On OFF mode, press OK for 10 seconds to enter the Installer Menu.
Press ◄ ► to select the options;
Press ▲ ▼ to change the values;
Press OK to exit the installer menu.
IMIT CONTROL SYSTEM s.r.l.
Via Varallo Pombia, 19 - Castelletto Sopra Ticino (NO)
Tel (+39)0331941600 - Fax (+39)0331973100
www.imit.it - info@controlsys.it
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Imit TECHNO DPT - Daily Programmable Thermostat Manual
Advertisement
Need help?
Do you have a question about the TECHNO DPT and is the answer not in the manual?
Questions and answers