ABB REL 551-C1 2.3 Series Installation And Commissioning Manual page 82

Line differential protection terminal
Table of Contents

Advertisement

76
Definite and inverse time-delayed
residual overcurrent protection (TEF)
65°
Iset
Figure 15: Measuring characteristic of the directional element.
6.
To activate the directional function, set Direction = Direction-
al.
7.
Set the polarising voltage to 2% of U
tween voltage and current to 65°.
8.
Check the operate current of the IMin function.
The function activates the TEF--START output.
9.
When independent time delay (definite) is selected, check the
operate time of the t1 timer by injecting a current two times
the set IMin operate value.
When inverse time delay is selected, check the operate time at
three points of the inverse characteristic. The formulas for operate
time for different types of inverse time delay curves are shown in
table 10.
Verifying settings by secondary
Upol = -3U
ϕ
IN Operation
and the phase angle be-
b
Chapter 11
injection
0
99000052.vsd