Configure the interface modules for V.36,
X.21 and RS530
Designation Explanation
REQ SEND
Request to send (follows auxiliary voltage)
RXD
Received data
SCREEN
Connection of cable screen
TCLK DCE
Transmitter signal timing from DCE
TCLK DTE
Transmitter signal timing from DTE
TXD
Transmitter data
For the co-directional operation the transmission rate of the transmitted signal must be
set.This setting, 56 or 64 kbit/s, is done on the HMI under:
Configuration/TerminalCom/RemTermCom/BitRate
For X.21 and contra-directional operation no settings are available.
For the signals used by the protection, the communication module for V.36 also fulfils
the older recommendation for V.35.