3.3
3.4
Making the electrical connections

Connecting to protective ground

Connect the unit to the grounding bar of the cubicle with a green/yellow conductor,
cross section at least 1.5 mm
at the back of the terminal.

Making the screen connection

When using screened cables always make sure screens are grounded and connected in
according to applicable engineering methods. This may include checking for appropri-
ate grounding points near the terminal, for instance, in the cubicle and/or near the source
of measuring. Ensure that ground connections are made with short (max. 10 cm) con-
ductors of an adequate cross section, at least 6 mm
tions.
Load
Source
2
(AWG18), connected to the protective ground connector
2
(AWG18) for single screen connec-
Signal Cable
Chapter 5
Installing the terminal
Source
Load
en01000189.vsd
27