Automatic Tests
The unit will automatically initiate a self-test/
self-diagnostic cycle based on the following table:
Testing Period
Duration of Test
Once a month
1 minute
Alternating: 30 minutes
Once every 6 months
or 90 minutes
Pressing test switch or flashing laser sensor at any time after a 90 minute test cycle has begun cancels the
remainder of the 90 minute test and returns the unit to normal operation. See page 3 for laser pointer test
details.
Service/Maintenance
Maintenance
This emergency lighting unit should be tested and maintained in accordance with National Electrical Code and NFPA 101 Life Safety
Code requirements. It is recommended that emergency light fixtures be tested for 30 seconds once a month and for 90 minutes once a
year.
Taking A Unit Out Of Service
If a unit is to be deliberately taken out of service for an extended period, the battery lead connector should be disconnected from the
charger circuit board and insulated so that the battery will go into storage in a fully charged condition.
Replacing The Battery
1. De-energize the AC power.
2. Remove the cover.
3. Disengage the battery harness from the charger PCB harness.
4. Disconnect the battery strap and remove battery pack.
5. Replace with new battery (see unit model label or battery label for correct p/n)
and repeat steps above in reverse.
Replacing LED Lamps
The LED lamps inside the unit are not replaceable or field serviceable. Please see dual-lite.com for further assistance.
Troubleshooting
Emergency circuit does not work
• Batteries are shipped uncharged and disconnected. Connect battery leads and charge 24 hours before testing.
• Make sure the charger board and test button/light pipe are properly seated and aligned.
• Check wiring connections
RECYCLING INFORMATION
All steel, aluminum and thermoplastic parts are recyclable.
NOTICE: Emergency units contain rechargeable batteries which
must be recycled or disposed of properly.
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to
change without notice. All values are design or typical values when measured under
laboratory conditions.
OPERATION
Manual Tests
By using the unit's test switch or laser pointer, one
can initiate different duration test cycles based on
the following table:
Initiating Action
Press test switch/flash sensor once
Press test switch/flash sensor twice 90 minutes
Test Cycle
1 minute
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed
READ AND FOLLOW ALL SAFETY
1.
Do not let power supply cords touch hot surfaces.
2.
Do not mount near gas or electric heaters.
3.
Equipment should be mounted in locations and at heights where it will not readily be
subject to tampering by unauthorized personnel.
4.
The use of accessory equipment not authorized by the manufacturer may cause an
unsafe condition.
5.
Do not use this equipment for other than its intended purpose.
6.
Servicing of this equipment should be performed by qualified service personnel.
7.
Test cycling: the Life Safety Code (NFPA 101) requires testing of emergency lighting
units once a month for a minimum of 30 seconds, and once a year for a minimum of
90 minutes.
SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING- This product contains chemicals known to the State of Califorina to cause cancer, birth
defects, and/or other reproductive harm. Thoroughly wash hands after installing, cleaning, or otherwire
touching this product.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
Rev 10/10/22
93157888_D
DYNHL Series
High-Lumen LED Industrial Emergency Lighting Unit
Wet Location, NEMA 4X & Food Processing
Standard and Remote Capacity
Installation, Operation, and Service Instructions
including the following.
INSTRUCTIONS
INSTALLER:

Advertisement

loading

Summary of Contents for Current DualLite DYNHL Series

  • Page 1 DYNHL Series OPERATION Automatic Tests Manual Tests High-Lumen LED Industrial Emergency Lighting Unit The unit will automatically initiate a self-test/ By using the unit's test switch or laser pointer, one self-diagnostic cycle based on the following table: Wet Location, NEMA 4X & Food Processing can initiate different duration test cycles based on the following table: Standard and Remote Capacity...
  • Page 2 FIXTURE INSTALLATION FIXTURE INSTALLATION Wall, Ceiling or Pole Mounting 93055897 BLK (NEG -) RED (POS +) DYNHL Wiring Diagram 1. The DYNHL mounting plate can be mounted directly to a wall, ceiling or pole (using appropriate hardware). If “J-box” mounted and the plastic housing back K.O.