Option A: Wi-Fi Hotspot Connection

1
On your PC or wireless device, connect to the wireless hotspot named ECLYPSE-XXYYZZ where XXYYZZ
are the last 6 hexadecimal characters of the controller's MAC address.
2
Enter the default password for the hotspot: eclypse1234.
3
Enter the following URL in your web browser's address bar (Google Chrome is recommended):
https://192.168.0.1 to access the ECLYPSE Web Interface.
4
a. Set up the ECY-STAT to communicate as a client with your router.
b. Alternatively, set up the ECY-STAT with a static IP according to your network, in the absence of a
DHCP server. Consult your IT department if you need help with this configuration.

Option B: Wired IP Connection using DHCP Server

If no DHCP server is available, use Option A with Static IP configuration according to your network.
1
Plug both the ECLYPSE Connected Thermostat and your PC to a router acting as DHCP server.
2
Make sure your PC is on the same IP subnet as the ECLYPSE controller. Consult your IT department if you
need help with this configuration.
3
Refer to the About screen in the Main Menu user interface and enter the Ethernet IP address in your web
browser's address bar (Google Chrome is recommended) to access the ECLYPSE Web Interface.
You should allow one (1) minute after the home screen is displayed for the ECY-STAT to fully boot up
before accessing the Web Interface.

Next Steps...

Once you have connected the ECY-STAT(s) to a network, you may proceed with the configurations using
Distech Controls' XpressNetwork Utility to perform batch operations such as batch discovery, IP or WiFi
configurations...
Refer to the ECLYPSE Connected Thermostat (ECY-STAT) User Guide for more information.