The quick start programming steps detailed below provide a basic configuration of the system when the panel is first
powered up. It is assumed that all loops are correctly wired to the panel with no wiring/crossover faults.
Hint: CAST ZFP Programming Tools (Part No. ZTOOLS) are available that allow quick and easy input of
data, cause and effect programming, naming of devices, zones and groups, etc. Contact your supplier for details.
The following touchscreen buttons are available in the steps listed below:
- displays user menus
- returns to previous menu
- confirms changes/settings
- cancels changes/settings
Section numbers, e.g.
, reference sections in the full manual with additional information.
E
A
L
3 (AL3)
NTER
CCESS
EVEL
button on the panel's touchscreen to display the access level 1 menu options.
First, press
Then, press
button and the AL3 login window appears (shown below left).
Using the touchscreen's numeric keypad, enter the four-digit AL3 code (default code is:
When the code has been entered correctly, the AL3 menu options appear (shown below right).
'
S
P
T
D
ET
ANEL
S
IME AND
ATE
Enter AL3 (4444) press
similar to the one shown right appears.
Set the time and date using the touchscreen's numeric keypad and
buttons. Also, set/unset the daylight saving time (DST).
When correct, press the
button to return to the AL3 menus.
A
A
UTO
DDRESS
During an auto address the panel automatically assigns an address to
each loop device in sequentially wired order. An alternative function
to auto address is loop learn which is used with pre-addressed devices.
Enter AL3 (4444) > Commissioning Functions press
button. The window shown right appears for example. Select the
loop(s) you want the panel to auto address (Loop 1 and Loop 2 are
shown selected), then press the
button.
Follow the instructions displayed at the panel.
Investigate and rectify any messages reported as faults on the touchscreen
A
FTER A SUCCESSFUL AUTO ADDRESS YOU WILL HAVE A
Page 2 of 2
CAST ZFP - Quick Start Programming Guide
- scroll up
4444
button and a window
.
"
,
ONE OUT
ALL OUT
!
ALARM SYSTEM
Manufacturer: Computionics Limited (C-TEC), Challenge Way, Martland Park, Wigan, Lancashire WN5 0LD.
E
D
DITING
EVICE DETAILS
Enter AL3 (4444) > Engineering Functions press
shown below left appears. Select a loop (loop 1 is shown selected) and a window similar to the one shown below
right appears.
- scroll down
Select a loop device (device 1 is shown selected above) and a window similar to the one shown below left appears.
).
Press
the selected device's parameters to be edited including device type, zone, input / output group and device name
"
FIRE
www.c-tec.com
(
)
WITHOUT USING ZTOOLS
button. A window similar to the one
button and a window similar to the one shown above right appears. This display allows
Approved Document No. DFU5030010 Rev 2
.