Quick Installation Guide
Version 1.0
S6-GR1P(7-8)K2
Ginlong Technologies Co., Ltd.
Note:
Installation Manual Download
For access to the manual please scan
the QR code below or you can go the URL
https://www.ginlong.com/global/
service.html
After entering the page, you can click "
icon to change to preferred language.
1
Bottom of the Inverter
Some models may have a different number of DC inputs,
please refer to datasheet/nameplate/actual product.
DC Switch(optional)
CT or meter input
DC input
RS 485
DRM
If no PV string connects to the DC input terminals, please install
the watertight cap onto the empty DC input terminals to guarantee
the inverter ingress protection rating.
2
Installation Clearance
Minimum clearance is required.
300mm
300mm
3
Mounting Hole Size
Use a 10mm drill bit to drill a hole of 60mm depth.
"
4
Inverter Installation
AC output
Ensure the mounting bracket is horizontal and use a Phillips
screwdriver to fasten the expansion bolts.
Lift the inverter and hang it on the bracket.
5
DC Connector Wiring and Assemble
Use a wire crimper to fasten the metal connector and insert it
into the top of the AMPHENOL connector. Use the AMPHENOL
special tool to fasten the AMPHENOL assembly.
outer diameter
2.5-4mm²
outer diameter
300mm
2.5-4mm²
Crimping plier
Locking screws
7±0.5mm
7±0.5mm
Note: Locator wings should not be crimped
AMPHENOL special tool
(-)
(+)

Advertisement

loading
Need help?

Need help?

Do you have a question about the S6-GR1P7K2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SOLIS S6-GR1P7K2

  • Page 1 Mounting Hole Size Note: Installation Manual Download For access to the manual please scan Use a 10mm drill bit to drill a hole of 60mm depth. the QR code below or you can go the URL https://www.ginlong.com/global/ service.html After entering the page, you can click " "...
  • Page 2 Assemble the AC Cable Install the Datalogger The steps to assemble the AC grid terminal connectors are Connect the AC grid connector to the inverter, until hearing Note: Turn off the AC and DC circuits before the installation 1. Insert communication stick to COM port. listed as follows: a slight click sound that indicates the connection succeed.

This manual is also suitable for:

S6-gr1p8k2