Thank you for choosing a NIVELCO instrument.
1. GENERAL INDTRODUCTION, OPERATION
NIVOFLIP MAK–100– type magnetic level switches are suitable for level switching of variuos liquids.
MAK–100 type magnetic level switches are used for magnetic-lamella bypass level indicator (named
NIVOFLIP) as an optional level switch.
O
:
PERATION PRINCIPLE
Mounted on suitable connection flanges on the side of the tank the liquid level in the bypass tube and the
tank is equal. In the stainless-steel bypass tube a magnetic float tracks the level of the liquid. In the float
a permanent magnet is incorporated, which operates the MAK-100 type adjustable positioned magnetic level
switch through the stainless-steel side of the tube, and provides non-contact signal transfer to the
microswitch.
Electronic connection is performed with cable gland, wired with a maximal 2.5 mm
Installation of the level switch is made by 2 pieces of hose clamps. Position of the switch can be changed to
adjust the needed switching level. The level switches are available in normal and Ex versions.
2. TECHNICAL DATA
Type
MAK–100–0
max. +130 °C
Medium temperature
(+266 °F)
–20... +80 °C
Ambient temperature
(–4... +176 °F)
Material of the switch-housing
Switch
250 V AC12 2.5 A
Switch rating
220 V DC13 0.3 A
Electrical connections
Mechanical protection
Electrical protection
Ex marking
Mass
* The Ex d and Ex m protection mode apply to the built-in microswitch!
2.1 G
ENERAL DATA
Class
Max. medium temperature
Ambient temperature
2.2 A
CCESSORIES
User's manual
Warranty card
EU Declaration of Conformity
2 pcs. Hose clamps
2.5 M
OUNTING
BKI11ATEX0004X ▪ mak1100a0600h_02 ▪1/2
MAK–100–6
See: Temperature classes table
Paint coated aluminium cast
1 microswitch, with NO / NC contacts
Only Ex ia certified and
approved contact isolator
should be used for supply!
cable gland: M20x1.5 terminal for max. 2.5 mm
IP65
Class I
–
II 1G
1.5 kg (3.3 lbs)
Temperature classes
T6
+80 °C (+176 °F)
+95 °C (+203 °F)
–20...+60 °C
(–4...+140 °F)
2.3 O
RDER CODE
NIVOFLIP MAK – 100 –
Type
Normal
Ex II 1G (ATEX)
II 2G Ex db eb mb IIC T6...T4 (ATEX)
2.6 M
OUNTING RECOMMENDATION
Default start-up:
Before start-up move the float to the top end, and all the way back to the bottom point.
2
cross sectioned cable.
MAK–100–7
250 V AC12 2.5 A
220 V DC13 0.3 A
(AWG14) wire cross section
2
II 2G Ex db eb mb IIC T6...T4
T5
T4
+130 °C (+266 °F)
–20...+70 °C
–20...+80 °C
(–4...+158 °F)
(–4...+176 °F)
Code
0
6
7
2.4 D
IMENSIONS