NIVELCO UNICONT PDF Installation And Programming Manual

NIVELCO UNICONT PDF Installation And Programming Manual

Loop indicator and converter to hart

Advertisement

Quick Links

pdf401en2108p
1 / 20

Advertisement

Table of Contents
loading

Summary of Contents for NIVELCO UNICONT PDF

  • Page 1  pdf401en2108p 1 / 20...
  • Page 2 Approvals Reference document number BKI ATEX, Certificate No.: BKI15ATEX0013 X/1 pdf4012m0600p_06 INMETRO, Certificate No.: DNV 15.0064 X – Rev. 01 pdf4012p0600p_06  2 / 20 pdf401en2108p...
  • Page 3: Table Of Contents

    C O N T E N T S INTRODUCTION ......................................5     ORDER CODES ......................................5     TECHNICAL DATA ....................................... 6     ......................................6     ENERAL DATA ......................... 7     DDITIONAL DATA FOR EXPLOSION PROOF CERTIFIED VERSIONS 3.2.1.
  • Page 4  4 / 20 pdf401en2108p...
  • Page 5: Introduction

    1. INTRODUCTION The UNICONT PDF–01 and PDF–01–6 / A / C Ex devices are 2-wire on-site indicators that can be inserted into a 4...20 mA current loop without the need for additional power supply. Since the displayed value is proportional to the input, the units are suitable for indication of temperature, pressure, level, etc. values, the information carried by the loop current.
  • Page 6: Technical Data

    3. TECHNICAL DATA 3.1 G ENERAL DATA PDF–01–2, PDF–401–A E PDF–01–6 E , PDF–601–A E PF–01–4, PF–401–B Ex, PF–01–8 Ex, PDF–401–C E PDF–601–C E PF–401–D E PF–601–B Ex, PF–601–D E Powering 2-wire 3-wire Input signal 4...20 mA current loop Measurement range 3.6…22 mA 0…22 mA Display / indication...
  • Page 7: Additional Data For Explosion - Proof Certified Versions

    3.2 A DDITIONAL DATA FOR EXPLOSION PROOF CERTIFIED VERSIONS 3.2.1. ATEX A : BKI15ATEX0013 X/1 PPROVAL PDF–401–6E PDF–401–A E PDF–401–C E Type PDF–501–6E PDF–601–6E PDF–601–A E PDF–601–C E Powder-coated aluminum Housing PBT glass fibre reinforced Powder-coated aluminum (EN AC-43100) or stainless steel (EN AC-42000) or stainless steel Protection type Intrinsically safe...
  • Page 8: Inmetro Approval

    3.2.2. INMETRO A : DNV 15.0064 X – R . 01 PPROVAL PDF–401–6E PF–401–8E Type PDF–401–C E PF–401–D E PDF–501–6E PF–501–8E PBT glass fibre reinforced or powder-coated aluminum Powder-coated aluminum Housing Intrinsically safe Flame proof enclosure and intrinsically safe Protection type Ex marking Ex ia IIC Ex ia IIB...
  • Page 9: Accessories

    AND STORAGE CONDITIONS UNICONT PDF units do not require maintenance on a regular basis. Repair during or after the guarantee period should only be carried out by NIVELCO. Before returning the device for repairs, it must be cleaned carefully, the parts in contact with the medium that might contain harmful substances must be decontaminated. Our official form (Returned Equipment Handling Form) must be enclosed.
  • Page 10 Wiring of a 2-wire UNICONT in the current loop of a transmitter Wiring of 3-wire UNICONTs with MultiCONT controller and 2-wire transmitters Wiring of a HART capable (3-wire) UNICONT in the current loop of a transmitter Wiring of 3-wire UNICONTs with MultiCONT controller and 4-wire transmitters Wiring of a HART capable (3-wire) UNICONT in the current loop of a 4-wire transmitter ...
  • Page 11: Safety Regulations For The E X Certified Units

    Internal wiring of the 2-wire UNICONT Internal wiring the of 3-wire UNICONT 4.2 S AFETY REGULATIONS FOR THE ERTIFIED UNITS – WARNING! DO NOT OPEN WHILE ENERGIZED! – Devices should be grounded by connecting their grounding screws to the equipotential system. –...
  • Page 12: Putting Into Operation, Programming

    5. PUTTING INTO OPERATION, PROGRAMMING Lighting of the VALID LED indicates that the UNICONT, installed and wired correctly, will operate according to the Manufacturer’s settings (see 5.1. Default). The device operates in MEASUREMENT mode. It is indicated by the format of the displayed value and that the PROG display is not lit.
  • Page 13: Display Of The Sap-202 And Keys Of The Unit

    5.2 D SAP-202 ISPLAY OF THE AND KEYS OF THE UNIT Symbols on the screen Symbols and sign on the frame   DIST – distance displayed (when ON) M – metric system   LEV – level displayed (when ON) US –...
  • Page 14 one-digit parameter address (0, 1, … 9) xxxxx five characters after the colon “:” possible – indications in place of X Bargraph (– dark) – two-digit parameter address (10, 11, … 19) dcba four characters after the colon “:” ( during programming parameter value “a”...
  • Page 15: Parameters - Description And Programming

    *Make sure that is pressed first! Remarks Double key pressing is indicated by ‘+’ If, after pressing , blinking does not jump over from the parameter address to the parameter value, then this means that  the parameter is either read-out type, or ...
  • Page 16 Setting displayed value (Da) to be assigned to input current Ia (See figures) FACTORY DEFAULT: 0.0 Setting displayed value (Db) to be assigned to input current Ib FACTORY DEFAULT: 100.0 Setting output current pertaining to the input current Ia (for 3-wire models only) FACTORY DEFAULT: 4 mA Setting output current pertaining to the input current Ib (for 3-wire models only)
  • Page 17 P11: dcba Setting range,* damping, noise suppression, error indication on the output current * FACTORY DEFAULT: 0000 Range can be selected with the 3-wire models for 4...20 mA or 0…20 mA. Setting is important in respect to the output current error indication. Damping can be used to reduce unwanted fluctuation of the displayed value Noise suppression is for eliminating possible disturbance coming from the mains Error indication on the current output of the 3-wire models is used to indicate error signals arriving as input current and the error of the...
  • Page 18 P12: dcba Displayed process values and their units FACTORY DEFAULT: 0100 The columns of the chart below can be programmed separately and it is supposed to be done reasonably (i.e. to have symbol LEV lit: 2 should be set under b, to have relevant unit lit (m/ft or cm/in) 2 or 3 should be set under a and setting 1 under d should be chosen if the required unit is meter or centimetre.
  • Page 19 Impgal/s kg/dm kg/s STon/yd gal/s kg/min ft/h Mgal/d kg/h kg/d HJ/h ML/d MetTon/min in/s ft/s Codes over 240 are engineering units defined by NIVELCO They might be different at other manufacturers.  pdf401en2108p 19 / 20...
  • Page 20: Error Indications

    RROR INDICATION ON THE OUTPUT CURRENT FOR 3 WIRE MODELS ONLY Output current is 3.8 mA or 22 mA, depending on setting of character d in P11 pdf401en2108p January 2021 NIVELCO reserves the right to change technical specifications without notice.  20 / 20 pdf401en2108p...

Table of Contents