Convenience Receptacle (Field Powered)
A Ground Fault Circuit Interrupter (GFCI) convenience
receptacle is provided in the main control box on all units. To
use this receptacle, connect a separate field-supplied 115 V
power wiring circuit to the outlet.
Figure 48: Unit Powered GFCI Receptacle Schematic
IM 1125-5
Convenience Receptacle (Unit Powered)
A Ground Fault Circuit Interrupter (GFCI) convenience
receptacle is provided in the main control box on all units.
The receptacle shall be powered by a factory installed and
wired 120V, 20 amp power supply. The power supply shall
be wired to the line side of the unit's main disconnect, so the
receptacle is powered when the main unit disconnect is off.
This option shall include a GFI receptacle, transformer, and
a branch circuit disconnect. The electrical circuit shall be
complete with primary and secondary overload protection.
See
Figure 48
for a branch circuit diagram.
Unit Options
Unit Options
53