Floor Console Recessed - Toshiba MMU-UP0071MH-UL Service Manual

Hide thumbs Also See for MMU-UP0071MH-UL:
Table of Contents

Advertisement

11-4. Floor Console Recessed

WARNING
Be sure to stop operation of the air conditioner before
work and then turn off switch of the breaker.
No. Part name
1. Detachment
Electric
parts
1) Remove the side cover.
assembly
(M4 screws: 2 pieces)
2) Remove conduit fixing plate.
(M4 screws: 2 pieces)
3) Remove the side plate (Front).
(M4 screws: 4 pieces)
4) Remove the side plate (Upper).
(M4 screws: 4 pieces)
5) Remove the dashboard of lead.
(M4 screw: 1 piece)
6) Remove the lead cover.
(No screw fixing)
7) Remove connecting connectors (TC1, TC2, TCJ, TA
sensor, PMV lead) of the control P.C. board. Take of
the lead wire from the clamp of the electric parts box.
CN100 ... TC1 (3P; Brown)
CN101 ... TC2 (2P; Black)
CN102 ... TCJ (2P; Red)
CN104 ... TA (2P; Orange)
CN210 ... Fan motor (7P; White)
CN104 ... PMV (6P; Blue)
* Remove the connectors by unlocking the locks of the
housing part.
8) Take off the fixing screws of the electric parts
assembly fixing screws, slide the electric parts
assembly toward upper side, and then remove it.
(M4 screws: 2 pieces)
2. Attachment
Following to the works in 1 of and 1) to 8), attach the parts
as original in the reverse procedure.
* Attach the lead cover by inserting the pawls of the piping
covers into the square holes of the electric parts
assembly.
* Attach the lead dashboard also by inserting the pawls of
the lead covers into the square holes of the lead cover.
Procedure
TC1, TC2, TCJ, TA sensors,
PMV lead
Clamp
Control P.C. board
Fan motor lead
Clamp
CAUTION
Be sure to put on gloves during working time;
otherwise an injury will be caused by a part etc.
– 152 –