Toshiba MMU-UP0071MH-UL Service Manual page 124

Hide thumbs Also See for MMU-UP0071MH-UL:
Table of Contents

Advertisement

[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out.
<RBC-AWSU5∗ ∗ ∗ ∗ ∗ >
Step 1
Push [
Menu] to open the "Menu".
Step 2
Push and hold [
• Push and hold 4 seconds.
Step 3
Push [
] and [
Step 4
Select "Indoor unit" , and the push [
Step 5
For group operation, all connected rooms in the system are displayed.
Select the unit whose EEPROM contents you want to read and push [
→ The fan of the selected indoor unit operates and the flap swings.
1. Push [
to 1.
(This is the setting for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
2. Change the CODE No. (DN) by pushing
Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2 to set the other settings in the same way and write down the setting data in the
manual that comes with the P.C. board.
(See pages 60 to 62).
∗ ∗ ∗ ∗ ∗
<RBC-AMTU3
>
[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out.
Step 1 Push
,
* When the group operation control is performed, the unit No. displayed for the first time is the
header unit No.
At this time, the CODE No. (DN) shows "
operation and the swing operation also starts if it has the louvers.
Step 2 Every time when the
control is displayed in order. Specify the indoor unit No. to be replaced.
1. Change e the CODE No. (DN) to
setting. (this is the setting for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
2. Change the CODE No. (DN) by pushing
Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data in
the manual that comes with the P.C. board. (See pages 60 to 62).
CODE No. required at least
DN
Contents
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
E0
Region
Step3 After writing down all setting data, push [ON/OFF] button to return to the normal stop status.
(It takes approx. 1 min until the remote controller operation is available again.)
Menu] and [
] to select "DN setting", and then push [
] to black highlight the code (DN), and then push [
and
button on the remote controller simultaneously for more than 4 seconds.
(left side button) button is pushed, the indoor unit No. under the group
UNIT LOUVER
1. The Code No. for the Indoor unit type and Indoor unit capacity are
required to set the rotation number setting of the fan.
2. If the system/indoor/group addresses are different from those
before replacement, the auto-address setting mode starts and the
manual resetting may be required again.
(when the multiple units group operation including twin system.)
] at the same time to open "Field setting menu".
Set/Fix]
/
buttons.
10
". Also, the fan of the indoor unit selected starts its
10 10 10 10 10
01 01 01 01 01
by pushing
→ → → → →
/
buttons for the temperature setting.
– 124 –
Set/Fix].
Set/Fix].
] and [
] to set the code No.
/
buttons for the temperature