Toshiba MMC-UP0181HP-UL Service Manual page 37

Hide thumbs Also See for MMC-UP0181HP-UL:
Table of Contents

Advertisement

<RBC-AWSU52-UL>
(1)
(2)
(3)
Note) The test run returns to the normal operation after 60 minutes.
1
In the "Field setting menu" screen, press
[
] and [
then press [
 Test mode is set, and returns to the "Field setting
menu" screen. Press the [
to open screen (2).
2
Press [
 Operation starts, and in test mode screen (1) opens.
(While stopped, it is screen (2))
 Test mode is done while the operating mode is set to
"Cool" or "Heat".
 The temperature cannot be set in test mode.
 Check codes are displayed in the normal way.
3
After completing test mode, in the "Field
setting menu" screen, press [
to select "Test mode", and then press
[
Set/Fix]
 Screen (3) appears.
 Press [
Set/Fix] to end test mode and do normal
operation.
- 37 -
] to select "Test mode", and
Set/Fix]
Return] button 2 times,