Cooling/Heating test run check
The test run for cooling/heating can be performed from either indoor remote controller or outdoor interface
P .C. board.
1. Start/Finish operation of test run
Test run from indoor remote controller
Wired remote controller: Refer to the below item of "Test run" of the wired remote controller.
Wireless remote controller: Refer to the next page item of "Test run" of the wireless remote controller.
Procedure
Push [TEST] button for 4 seconds or more.
1
[TEST] is displayed at the display part and
the mode enters in TEST mode.
2
Push [ON/OFF] button.
Change the mode from [COOL] to [HEAT] using [MODE] button.
Do not use [MODE] button for other mode except
3
[COOL]/[HEAT] modes.
The temperature cannot be adjusted during test run.
The error detection is performed as usual.
After test run, push [ON/OFF] button to stop the operation.
4
(Display on the display part is same to that in Procedure
Push [TEST] button to clear the TEST mode.
5
([TEST] display in the display part disappears and
status becomes the normal stop status.)
Note) The test run returns to the normal operation after 60 minutes.
In case of wired remote controller
<RBC-AMT32UL>
TEMP.
TIMER SET
TIME
FILTER
1,
RESET
TEST
SET
CL
5
Operation contents
- 36 -
2,
ON / OFF
4
FAN
MODE
3
SAVE
VENT
SWING/FIX
UNIT LOUVER
1
.)
TEST
TEST

Advertisement

Table of Contents
loading

Table of Contents